eq600-2:GeographicalRegionCountShape

Severity: sh:Violation

Targets:

  • targetNode: cim:GeographicalRegion

eq600-2:ReactiveCapabilityCurve

Severity: sh:Violation

Targets:

  • targetClass: cim:ReactiveCapabilityCurve

Nested Properties:

eq600-2:ReactiveCapabilityCurve-units

Path: rdf:type
For a ReactiveCapabilityCurve associated with SynchronousMachine, the Curve.xUnit shall be set to UnitSymbol.W and both Curve.y1Unit and Curve.y2Unit shall be set to UnitSymbol.VAr. As the multiplier is not included in the profile it is defined the same as the multiplier used for datatype ActivePower and ReactivePower, i.e. UnitMultiplier.M.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this
WHERE {
$this ^cim:SynchronousMachine.InitialReactiveCapabilityCurve/rdf:type cim:SynchronousMachine .
$this cim:Curve.xUnit ?xunit .
$this cim:Curve.y1Unit ?y1unit .
$this cim:Curve.y2Unit ?y2unit .
BIND(EXISTS{$this cim:Curve.y2Unit ?y2unitcheck} AS ?hasy2unit).
FILTER (?hasy2unit=false && ?xunit!=cim:UnitSymbol.W && ?y2unit!=cim:UnitSymbol.VAr && ?y1unit!=cim:UnitSymbol.VAr).
}
  • Messages: ["Not correct or not provided units of a ReactiveCapabilityCurve of a SynchronousMachine."]

eq600-2:RotatingMachine

Severity: sh:Violation

Targets:

  • targetClass: cim:SynchronousMachine
  • targetClass: cim:AsynchronousMachine

eq600-2:SubstationCountShape

Severity: sh:Violation

Targets:

  • targetNode: cim:SubstationCount

Nested Properties:

eq600-2:Substation-count

Path: rdf:type
The number of Substation-s shall reflect the design of the power system. Cases of a single Substation in a power system model or having a Substation per VoltageLevel are reported as warnings.

Severity: sh:Warning

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Warning)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?substations ?voltagelevels
WHERE {
{
SELECT $this (COUNT(?ss) AS ?substations)
WHERE {
?ss rdf:type cim:Substation .
}
GROUP BY $this
}
{
SELECT $this (COUNT(?vl) AS ?voltagelevels)
WHERE {
?vl rdf:type cim:VoltageLevel .
}
GROUP BY $this
}

FILTER (?substations=1 || ?substations=?voltagelevels).
}
  • Messages: ["The model has either one Substation or a Substation per VoltageLevel. Number of Substation-s: {?substations}. Number of VoltageLevel-s: {?voltagelevels}."]

eq600-2:TapChanger

Severity: sh:Violation

Targets:

  • targetClass: cim:RatioTapChanger
  • targetClass: cim:PhaseTapChangerTabular
  • targetClass: cim:PhaseTapChangerSymmetrical
  • targetClass: cim:PhaseTapChangerAsymmetrical
  • targetClass: cim:PhaseTapChangerLinear

Nested Properties:

eq600-2:TapChanger.neutralU-valueRangePair

Path: cim:TapChanger.neutralU
The TapChanger.neutralU shall be the same as PowerTransformerEnd.ratedU.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this $PATH ?value .
OPTIONAL {$this cim:RatioTapChanger.TransformerEnd/cim:PowerTransformerEnd.ratedU ?rratedu } .
OPTIONAL {$this cim:PhaseTapChanger.TransformerEnd/cim:PowerTransformerEnd.ratedU ?pratedu } .
FILTER ((bound(?rratedu) && ?value!=?rratedu) || (bound(?pratedu) && ?value!=?pratedu)).
}
  • Messages: ["The value is not the same as the PowerTransformerEnd.ratedU."]