eq:ACDCConverter​

Severity: sh:Violation

Targets:

  • targetClass: cim:CsConverter
  • targetClass: cim:VsConverter

eq:ACDCTerminal​

Severity: sh:Violation

Targets:

  • targetClass: cim:ConformLoad
  • targetClass: cim:Disconnector
  • targetClass: cim:DCBreaker
  • targetClass: cim:DCChopper
  • targetClass: cim:Switch
  • targetClass: cim:CsConverter
  • targetClass: cim:LinearShuntCompensator
  • targetClass: cim:GroundingImpedance
  • targetClass: cim:EnergyConsumer
  • targetClass: cim:AsynchronousMachine
  • targetClass: cim:Ground
  • targetClass: cim:DCSwitch
  • targetClass: cim:DCSeriesDevice
  • targetClass: cim:DCShunt
  • targetClass: cim:Junction
  • targetClass: cim:SeriesCompensator
  • targetClass: cim:VsConverter
  • targetClass: cim:NonConformLoad
  • targetClass: cim:StationSupply
  • targetClass: cim:PowerElectronicsConnection
  • targetClass: cim:GroundDisconnector
  • targetClass: cim:DCLineSegment
  • targetClass: cim:DCDisconnector
  • targetClass: cim:EquivalentInjection
  • targetClass: cim:EquivalentBranch
  • targetClass: cim:PowerTransformer
  • targetClass: cim:Clamp
  • targetClass: cim:BusbarSection
  • targetClass: cim:PetersenCoil
  • targetClass: cim:ExternalNetworkInjection
  • targetClass: cim:NonlinearShuntCompensator
  • targetClass: cim:EnergySource
  • targetClass: cim:StaticVarCompensator
  • targetClass: cim:Fuse
  • targetClass: cim:Jumper
  • targetClass: cim:LoadBreakSwitch
  • targetClass: cim:DisconnectingCircuitBreaker
  • targetClass: cim:Cut
  • targetClass: cim:DCBusbar
  • targetClass: cim:SynchronousMachine
  • targetClass: cim:EquivalentShunt
  • targetClass: cim:Breaker
  • targetClass: cim:DCGround
  • targetClass: cim:ACLineSegment

Nested Properties:

eq:ACDCTerminal.sequenceNumber-numbering​

Path: rdf:type
Name: C:301:EQ:ACDCTerminal.sequenceNumber:numbering
The sequence numbering starts with 1 and additional terminals should follow in increasing order. The first terminal is the starting point for a two terminal branch.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this (COUNT(?sn) AS ?countsn) (COUNT(DISTINCT ?sn) AS ?countdsn) (MIN(?sn) AS ?minsn) (SUM(?sn) AS ?sumsn) (COUNT(?terms) AS ?countterms)
WHERE {
$this (^cim:Terminal.ConductingEquipment)|(^cim:DCTerminal.DCConductingEquipment) ?terms.
?terms rdf:type ?type .
?terms cim:ACDCTerminal.sequenceNumber ?sn .
}
GROUP BY $this ?type
HAVING(?countsn!=?countdsn || ?minsn!=1 || (?countterms=1 && ?sumsn!=1) || (?countterms=2 && (?sumsn/2)!=1.5) || (?countterms=3 && (?sumsn/3)!=2))

  • Messages: ["There is no terminal with sequenceNumber=1 or the numbering is not unique."]

eq:ACLineSegment​

Severity: sh:Violation

Targets:

  • targetClass: cim:ACLineSegment

eq:ActivePowerLimit​

Severity: sh:Violation

Targets:

  • targetClass: cim:ActivePowerLimit

eq:ApparentPowerLimit​

Severity: sh:Violation

Targets:

  • targetClass: cim:ApparentPowerLimit

eq:AsynchronousMachine​

Severity: sh:Violation

Targets:

  • targetClass: cim:AsynchronousMachine

eq:BaseVoltage​

Severity: sh:Violation

Targets:

  • targetClass: cim:BaseVoltage

eq:BatteryUnit​

Severity: sh:Violation

Targets:

  • targetClass: cim:BatteryUnit

eq:BoundaryPoint​

Severity: sh:Violation

Targets:

  • targetClass: cim100:BoundaryPoint

eq:Breaker​

Severity: sh:Violation

Targets:

  • targetClass: cim:Breaker

eq:BusbarSection​

Severity: sh:Violation

Targets:

  • targetClass: cim:BusbarSection

eq:Clamp​

Severity: sh:Violation

Targets:

  • targetClass: cim:Clamp

eq:Clamp-numberOfTerminals​

Name: C:452:EQ:Clamp:numberOfTerminals
A Clamp is ConductingEquipment and has one Terminal with an associated ConnectivityNode.

Severity: sh:Violation

Messages:

  • "Either the Clamp does not have exactly one Terminal or the Terminal is not associated with a ConnectivityNode."

Targets:

  • targetClass: cim:Clamp

eq:ConductingEquipment-oneTerminal​

Name: C:301:EQ:ConductingEquipment:oneTerminal
All other ConductingEquipment leaf classes (notably also including Clamp and BusbarSection) and DCConductingEquipment have a single terminal.

Severity: sh:Violation

Messages:

  • "The ConductingEquipment does not have the required number of Terminal-s."

Targets:

  • targetClass: cim:EnergyConsumer
  • targetClass: cim:SynchronousMachine
  • targetClass: cim:AsynchronousMachine
  • targetClass: cim:DCGround
  • targetClass: cim:EnergySource
  • targetClass: cim:NonConformLoad
  • targetClass: cim:EquivalentInjection
  • targetClass: cim:Junction
  • targetClass: cim:DCBusbar
  • targetClass: cim:DCShunt
  • targetClass: cim:ExternalNetworkInjection
  • targetClass: cim:LinearShuntCompensator
  • targetClass: cim:StaticVarCompensator
  • targetClass: cim:EquivalentShunt
  • targetClass: cim:Ground
  • targetClass: cim:ConformLoad
  • targetClass: cim:StationSupply
  • targetClass: cim:PowerElectronicsConnection
  • targetClass: cim:NonlinearShuntCompensator

eq:ConductingEquipment-twoTerminals​

Name: C:301:EQ:ConductingEquipment:twoTerminals
The following ConductingEquipment classes have two terminals: ACLineSegment, DCLineSegment, DCSeriesDevice, DCSwitch (and its specializations), DCChopper, Switch and all its specializations (including Jumper, Fuse, Breaker, Disconnector, LoadBreakSwitch, and Cut), SeriesCompensator, and EquivalentBranch. The PowerTransformer class typically has two terminals, but may also have one or more terminals. For example a zig-zag connected grounding transformer may have one terminal. Three terminal transformers are commonly used in transmission systems and in special cases transformers may have four, five, or more terminals.

Severity: sh:Violation

Messages:

  • "The ConductingEquipment does not have the required number of Terminal-s."

Targets:

  • targetClass: cim:LoadBreakSwitch
  • targetClass: cim:DCLineSegment
  • targetClass: cim:DCSeriesDevice
  • targetClass: cim:GroundDisconnector
  • targetClass: cim:Breaker
  • targetClass: cim:DisconnectingCircuitBreaker
  • targetClass: cim:Cut
  • targetClass: cim:SeriesCompensator
  • targetClass: cim:DCBreaker
  • targetClass: cim:DCChopper
  • targetClass: cim:Switch
  • targetClass: cim:Disconnector
  • targetClass: cim:Jumper
  • targetClass: cim:EquivalentBranch
  • targetClass: cim:ACLineSegment
  • targetClass: cim:DCSwitch
  • targetClass: cim:DCDisconnector
  • targetClass: cim:Fuse

eq:ConductingEquipment-twoTerminalsShape​

Severity: sh:Violation

Targets:

  • targetClass: cim:ACLineSegment
  • targetClass: cim:DCBreaker
  • targetClass: cim:Jumper
  • targetClass: cim:DCLineSegment
  • targetClass: cim:DCSeriesDevice
  • targetClass: cim:DCDisconnector
  • targetClass: cim:DCChopper
  • targetClass: cim:GroundDisconnector
  • targetClass: cim:Breaker
  • targetClass: cim:EquivalentBranch
  • targetClass: cim:Switch
  • targetClass: cim:Fuse
  • targetClass: cim:LoadBreakSwitch
  • targetClass: cim:DisconnectingCircuitBreaker
  • targetClass: cim:Cut
  • targetClass: cim:SeriesCompensator
  • targetClass: cim:DCSwitch
  • targetClass: cim:Disconnector

Nested Properties:

eq:Terminal.phases-consistencyEquipment​

Path: rdf:type
Name: C:301:EQ:Terminal.phases:consistencyEquipment
The phase code on terminals connecting same ConnectivityNode or same TopologicalNode as well as for equipment between two terminals shall be consistent.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value2 ?value1
WHERE {
$this ^cim:Terminal.ConductingEquipment ?term1 .
?term1 cim:ACDCTerminal.sequenceNumber 1 .
$this ^cim:Terminal.ConductingEquipment ?term2 .
?term2 cim:ACDCTerminal.sequenceNumber 2
OPTIONAL {?term1 cim:Terminal.phases ?value1 } .
OPTIONAL {?term2 cim:Terminal.phases ?value2 } .
FILTER ((bound(?value1) && bound(?value2) && ?term1!=?term2 && (?value1=cim:PhaseCode.ABCN || ?value1=cim:PhaseCode.N) && (?value2!=cim:PhaseCode.ABCN && ?value2!=cim:PhaseCode.N)) ||
(bound(?value1) && bound(?value2) && ?term1!=?term2 && (?value1=cim:PhaseCode.ABC) && (?value2!=cim:PhaseCode.ABC)) ||
(bound(?value1) && !bound(?value2) && ?term1!=?term2 && (?value1=cim:PhaseCode.ABCN || ?value1=cim:PhaseCode.N))
) .
}
  • Messages: ["The phase codes for terminals of 2-terminal equipment are not consistent. Terminal 1 code:{?value1} Terminal 2 code: {?value2}."]

eq:ConductingEquipment.BaseVoltage​

Severity: sh:Violation

Targets:

  • targetClass: cim:Junction
  • targetClass: cim:NonlinearShuntCompensator
  • targetClass: cim:Disconnector
  • targetClass: cim:BusbarSection
  • targetClass: cim:EnergyConsumer
  • targetClass: cim:ConformLoad
  • targetClass: cim:PowerElectronicsConnection
  • targetClass: cim:SeriesCompensator
  • targetClass: cim:Switch
  • targetClass: cim:CsConverter
  • targetClass: cim:GroundingImpedance
  • targetClass: cim:StationSupply
  • targetClass: cim:EquivalentShunt
  • targetClass: cim:EquivalentBranch
  • targetClass: cim:Breaker
  • targetClass: cim:DisconnectingCircuitBreaker
  • targetClass: cim:Clamp
  • targetClass: cim:ACLineSegment
  • targetClass: cim:LinearShuntCompensator
  • targetClass: cim:AsynchronousMachine
  • targetClass: cim:Ground
  • targetClass: cim:NonConformLoad
  • targetClass: cim:EquivalentInjection
  • targetClass: cim:Jumper
  • targetClass: cim:VsConverter
  • targetClass: cim:SynchronousMachine
  • targetClass: cim:PowerTransformer
  • targetClass: cim:Fuse
  • targetClass: cim:GroundDisconnector
  • targetClass: cim:LoadBreakSwitch
  • targetClass: cim:PetersenCoil
  • targetClass: cim:EnergySource
  • targetClass: cim:ExternalNetworkInjection
  • targetClass: cim:StaticVarCompensator
  • targetClass: cim:Cut

Nested Properties:

eq:ConductingEquipment.BaseVoltage-usage​

Path: cim:Equipment.EquipmentContainer
Name: C:301:EQ:ConductingEquipment.BaseVoltage:usage
Use only when there is no voltage level container used and only one base voltage applies. For example, not used for transformers.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this $PATH ?value .
#?value rdf:type ?type .
?value rdf:type cim:VoltageLevel .
$this rdf:type ?condeqtype .
BIND(EXISTS{$this cim:ConductingEquipment.BaseVoltage ?basevoltage} AS ?hasbv).
#$this cim:ConductingEquipment.BaseVoltage ?basevoltage .
#FILTER (!isLiteral(?basevoltage) && ?type=cim:VoltageLevel && ?condeqtype!=cim:ACLineSegment && ?condeqtype!=cim:EquivalentBranch && ?condeqtype!=cim:SeriesCompensator) .
FILTER (?hasbv=true && ?condeqtype!=cim:ACLineSegment && ?condeqtype!=cim:EquivalentBranch && ?condeqtype!=cim:SeriesCompensator && ?condeqtype!=cim:Equipment) .
}
  • Messages: ["The association ConductingEquipment.BaseVoltage is defined for a ConductingEquipment contained in a VoltageLevel."]

eq:ControlAreaGeneratingUnit.GeneratingUnit​

Severity: sh:Violation

Targets:

  • targetClass: cim:HydroGeneratingUnit
  • targetClass: cim:NuclearGeneratingUnit
  • targetClass: cim:SolarGeneratingUnit
  • targetClass: cim:ThermalGeneratingUnit
  • targetClass: cim:GeneratingUnit
  • targetClass: cim:WindGeneratingUnit

Nested Properties:

eq:ControlAreaGeneratingUnit.GeneratingUnit-instance​

Path: rdf:type
Name: C:301:EQ:ControlAreaGeneratingUnit.GeneratingUnit:instance
Note that a control area should include a GeneratingUnit only once.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this (COUNT(?ca) AS ?count)
WHERE {
$this ^cim:ControlAreaGeneratingUnit.GeneratingUnit/cim:ControlAreaGeneratingUnit.ControlArea ?ca.
}
GROUP BY $this ?ca
HAVING(?count>1)

  • Messages: ["The GeneratingUnit is assigned to more than once in a ControlArea."]

eq:CsConverter​

Severity: sh:Violation

Targets:

  • targetClass: cim:CsConverter

Nested Properties:

eq:DCConverterUnit-cscPowerTransformer​

Path: rdf:type
Name: C:301:EQ:DCConverterUnit:cscPowerTransformer
For a CSC HVDC, the transformer shall be modelled explicitly.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this cim:Equipment.EquipmentContainer ?value .

FILTER NOT EXISTS {
?value ^cim:Equipment.EquipmentContainer/rdf:type cim:PowerTransformer
}.
}
  • Messages: ["A DCConverterUnit that contains CsConverter does not contain a PowerTransformer."]

eq:CurrentLimit​

Severity: sh:Violation

Targets:

  • targetClass: cim:CurrentLimit

eq:Cut​

Severity: sh:Violation

Targets:

  • targetClass: cim:Cut

eq:DCBreaker​

Severity: sh:Violation

Targets:

  • targetClass: cim:DCBreaker

eq:DCBusbar​

Severity: sh:Violation

Targets:

  • targetClass: cim:DCBusbar

eq:DCChopper​

Severity: sh:Violation

Targets:

  • targetClass: cim:DCChopper

eq:DCDisconnector​

Severity: sh:Violation

Targets:

  • targetClass: cim:DCDisconnector

eq:DCGround​

Severity: sh:Violation

Targets:

  • targetClass: cim:DCGround

eq:DCLineSegment​

Severity: sh:Violation

Targets:

  • targetClass: cim:DCLineSegment

eq:DCSeriesDevice​

Severity: sh:Violation

Targets:

  • targetClass: cim:DCSeriesDevice

eq:DCShunt​

Severity: sh:Violation

Targets:

  • targetClass: cim:DCShunt

eq:DCSwitch​

Severity: sh:Violation

Targets:

  • targetClass: cim:DCSwitch

eq:DisconnectingCircuitBreaker​

Severity: sh:Violation

Targets:

  • targetClass: cim:DisconnectingCircuitBreaker

eq:Disconnector​

Severity: sh:Violation

Targets:

  • targetClass: cim:Disconnector

eq:EarthFaultCompensator​

Severity: sh:Violation

Targets:

  • targetClass: cim:GroundingImpedance
  • targetClass: cim:PetersenCoil

eq:Equipment​

Severity: sh:Violation

Targets:

  • targetClass: cim:EquivalentBranch
  • targetClass: cim:EquivalentShunt
  • targetClass: cim:EquivalentInjection

Nested Properties:

eq:Equipment.aggregate-notUsed​

Path: cim:Equipment.aggregate
Name: C:301:EQ:Equipment.aggregate:notUsed
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
OPTIONAL {$this $PATH ?value }.
FILTER (bound(?value)) .
}
  • Messages: ["Not allowed property (attribute)."]

eq:EquivalentBranch​

Severity: sh:Violation

Targets:

  • targetClass: cim:EquivalentBranch

Nested Properties:

eq:EquivalentBranch.r21-usage​

Path: cim:EquivalentBranch.r21
Name: C:301:EQ:EquivalentBranch.r21:usage
This attribute is optional and represent unbalanced network such as off-nominal phase shifter. If only EquivalentBranch.r is given, then EquivalentBranch.r21 is assumed equal to EquivalentBranch.r.

Severity: sh:Info

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Info)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
OPTIONAL {$this $PATH ?value }.
$this cim:EquivalentBranch.r ?r .
FILTER (bound(?value) && ?value!=?r) .
}
  • Messages: ["Asymmetrical EquivalentBranch is modelled as EquivalentBranch.r is different from EquivalentBranch.r21."]

eq:EquivalentBranch.x21-usage​

Path: cim:EquivalentBranch.x21
Name: C:301:EQ:EquivalentBranch.x21:usage
This attribute is optional and represent unbalanced network such as off-nominal phase shifter. If only EquivalentBranch.x is given, then EquivalentBranch.x21 is assumed equal to EquivalentBranch.x.

Severity: sh:Info

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Info)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
OPTIONAL {$this $PATH ?value }.
$this cim:EquivalentBranch.x ?x .
FILTER (bound(?value) && ?value!=?x) .
}
  • Messages: ["Asymmetrical EquivalentBranch is modelled as EquivalentBranch.x is different from EquivalentBranch.x21."]

eq:EquivalentInjection​

Severity: sh:Violation

Targets:

  • targetClass: cim:EquivalentInjection

Nested Properties:

eq:EquivalentInjection.regulationCapability-associatedCurve​

Path: cim:EquivalentInjection.regulationCapability
Name: C:301:EQ:EquivalentInjection.regulationCapability:associatedCurve
ReactiveCapabilityCurve can only be associated with EquivalentInjection if the flag is true.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this $PATH ?value
OPTIONAL {$this cim:EquivalentInjection.ReactiveCapabilityCurve ?curve }.
FILTER (bound(?curve) && ?value=false) .
}
  • Messages: ["The value does not allow a ReactiveCapabilityCurve to be associated. "]

eq:Fuse​

Severity: sh:Violation

Targets:

  • targetClass: cim:Fuse

eq:GeneratingUnit​

Severity: sh:Violation

Targets:

  • targetClass: cim:GeneratingUnit

eq:GeneratingUnit.nominalP​

Severity: sh:Violation

Targets:

  • targetClass: cim:GeneratingUnit
  • targetClass: cim:WindGeneratingUnit
  • targetClass: cim:HydroGeneratingUnit
  • targetClass: cim:NuclearGeneratingUnit
  • targetClass: cim:SolarGeneratingUnit
  • targetClass: cim:ThermalGeneratingUnit

Nested Properties:

eq:GeneratingUnit.nominalP-valueRangePair​

Path: cim:GeneratingUnit.nominalP
Name: C:301:EQ:GeneratingUnit.nominalP:valueRangePair
The attribute shall be a positive value equal to or less than RotatingMachine.ratedS.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this $PATH ?value .
BIND(EXISTS{$this $PATH ?v} AS ?hasvalue).
#OPTIONAL {$this $PATH ?value }.
$this ^cim:RotatingMachine.GeneratingUnit/cim:RotatingMachine.ratedS ?rateds .
BIND(EXISTS{$this ^cim:RotatingMachine.GeneratingUnit/cim:RotatingMachine.ratedS ?r} AS ?hasrateds).
#OPTIONAL {$this ^cim:RotatingMachine.GeneratingUnit ?machine }.
#OPTIONAL {?machine cim:RotatingMachine.ratedS ?rateds }.
FILTER (?hasvalue=true && ?hasrateds=true && (?value<=0 || ?value>?rateds) ) .
}
  • Messages: ["The value is either negative, zero or greater than RotatingMachine.ratedS."]

eq:GroundDisconnector​

Severity: sh:Violation

Targets:

  • targetClass: cim:GroundDisconnector

eq:HydroGeneratingUnit​

Severity: sh:Violation

Targets:

  • targetClass: cim:HydroGeneratingUnit

eq:Jumper​

Severity: sh:Violation

Targets:

  • targetClass: cim:Jumper

eq:LimitKind​

Severity: sh:Violation

Targets:

  • targetClass: cim:OperationalLimitType

Nested Properties:

eq:LimitKind.patl-numberOfLimitType​

Path: rdf:type
Name: C:301:EQ:LimitKind.patl:numberOfLimitType
The OperationnalLimitType.isInfiniteDuration is set to true. There shall be only one OperationalLimitType of kind PATL per OperationalLimitSet if the PATL is ApparentPowerLimit, ActivePowerLimit, or CurrentLimit for a given Terminal or Equipment.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this (COUNT(?ol) AS ?patls) ?infdur ?value
WHERE {
$this cim:OperationalLimitType.isInfiniteDuration ?infdur .
$this eu:OperationalLimitType.kind eu:LimitKind.patl .
$this ^cim:OperationalLimit.OperationalLimitType ?ol .
?ol rdf:type ?typeol .
?ol cim:OperationalLimit.OperationalLimitSet ?value .
FILTER (?typeol IN (cim:ApparentPowerLimit , cim:ActivePowerLimit , cim:CurrentLimit)) .
}
GROUP BY $this ?value ?infdur
HAVING (?patls>1 || ?infdur=false)

  • Messages: ["Either there is more than one PATL defined for a given OperationalLimitSet or OperationnalLimitType.isInfiniteDuration is not set to true for PATL type. The OperationnalLimitType.isInfiniteDuration is: {?infdur}."]

eq:LimitKind.tc-duration​

Path: rdf:type
Name: C:301:EQ:LimitKind.tc:duration
The duration is always zero if the OperationalLimitType.acceptableDuration is exchanged. Only one limit value exists for the TC type.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this (COUNT(?ol) AS ?tcs) ?adur ?value
WHERE {
$this eu:OperationalLimitType.kind eu:LimitKind.tc .
$this ^cim:OperationalLimit.OperationalLimitType ?ol .
?ol cim:OperationalLimit.OperationalLimitSet ?value .
OPTIONAL {$this cim:OperationalLimitType.acceptableDuration ?adur }.
}
GROUP BY $this ?value ?adur ?value
HAVING (?tcs>1 || (bound(?adur) && ?adur!=0))

  • Messages: ["Either OperationalLimitType.acceptableDuration is present and different than 0 or there is more than one limit with TC type. The OperationnalLimitType.acceptableDuration is: {?adur}."]

eq:LinearShuntCompensator​

Severity: sh:Violation

Targets:

  • targetClass: cim:LinearShuntCompensator

Nested Properties:

eq:ShuntCompensator.nomU-nominalVoltageDifference​

Path: rdf:type
Name: C:301:EQ:ShuntCompensator.nomU:nominalVoltageDifference
This should normally be within 10% of the voltage at which the capacitor is connected to the network.

Severity: sh:Warning

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Warning)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this cim:ShuntCompensator.nomU ?value .
$this cim:Equipment.EquipmentContainer/cim:VoltageLevel.BaseVoltage/cim:BaseVoltage.nominalVoltage ?nomv .

FILTER (?value<0.9*?nomv && ?value>1.1*?nomv) .
}
  • Messages: ["The value differs with more than 10% of the nominal voltage abtained via the containment to VoltageLevel."]

eq:LoadBreakSwitch​

Severity: sh:Violation

Targets:

  • targetClass: cim:LoadBreakSwitch

eq:LoadResponseCharacteristic​

Severity: sh:Violation

Targets:

  • targetClass: cim:LoadResponseCharacteristic

Nested Properties:

eq:LoadResponseCharacteristic.exponentModel-exponentCoefficient​

Path: cim:LoadResponseCharacteristic.exponentModel
Name: C:301:EQ:LoadResponseCharacteristic.exponentModel:exponent|C:301:EQ:LoadResponseCharacteristic.exponentModel:coefficient|C:301:EQ:LoadResponseCharacteristic.exponentModel:coefficientSum
Indicates the exponential voltage dependency model is to be used. If false, the coefficient model is to be used. The exponential voltage dependency model consist of the attributes:- pVoltageExponent; - qVoltageExponent; - pFrequencyExponent; - qFrequencyExponent. The coefficient model consist of the attributes:- pConstantImpedance; - pConstantCurrent; - pConstantPower; - qConstantImpedance; - qConstantCurrent; - qConstantPower. The sum of pConstantImpedance, pConstantCurrent and pConstantPower shall equal 1. The sum of qConstantImpedance, qConstantCurrent and qConstantPower shall equal 1.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this $PATH ?value .

OPTIONAL {$this cim:LoadResponseCharacteristic.pFrequencyExponent ?pfe }.
OPTIONAL {$this cim:LoadResponseCharacteristic.pVoltageExponent ?pve }.
OPTIONAL {$this cim:LoadResponseCharacteristic.qFrequencyExponent ?qfe }.
OPTIONAL {$this cim:LoadResponseCharacteristic.qVoltageExponent ?qve }.
OPTIONAL {$this cim:LoadResponseCharacteristic.pConstantCurrent ?pcc }.
OPTIONAL {$this cim:LoadResponseCharacteristic.pConstantImpedance ?pci }.
OPTIONAL {$this cim:LoadResponseCharacteristic.pConstantPower ?pcp }.
OPTIONAL {$this cim:LoadResponseCharacteristic.qConstantCurrent ?qcc }.
OPTIONAL {$this cim:LoadResponseCharacteristic.qConstantImpedance ?qci }.
OPTIONAL {$this cim:LoadResponseCharacteristic.qConstantPower ?qcp }.

FILTER ((?value=true && (!bound(?pfe) || !bound(?pve) || !bound(?qfe) || !bound(?qve) || bound(?pcc) || bound(?pci) || bound(?pcp) || bound(?qcc) || bound(?qci) || bound(?qcp))) ||
(?value=false && (bound(?pfe) || bound(?pve) || bound(?qfe) || bound(?qve) || !bound(?pcc) || !bound(?pci) || !bound(?pcp) || !bound(?qcc) || !bound(?qci) || !bound(?qcp))) ||
(?value=false && bound(?pcc) && bound(?pci) && bound(?pcp) && bound(?qcc) && bound(?qci) && bound(?qcp) && (?pcc+?pci+?pcp!=1 || ?qcc+?qci+?qcp!=1) )
) .
}
  • Messages: ["One of the following occurs: 1) Missing required properties (attributes) for either exponential voltage dependency model or exponential model. 2) There is a mixture between the attributes. 3) The sum of either all active power related coefficients or reactive power related coefficients does not equal 1."]

eq:NonlinearShuntCompensator​

Severity: sh:Violation

Targets:

  • targetClass: cim:NonlinearShuntCompensator

Nested Properties:

eq:ShuntCompensator.maximumSections-numberOfInstances​

Path: cim:ShuntCompensator.maximumSections
Name: C:301:EQ:NonlinearShuntCompensatorPoint:numberOfInstances
The number of NonlinearShuntCompenstorPoint instances associated with a NonlinearShuntCompensator shall be equal to ShuntCompensator.maximumSections.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value ?typesall
WHERE {
{
SELECT $this (COUNT(?typeall) AS ?typesall)
WHERE {
$this ^cim:NonlinearShuntCompensatorPoint.NonlinearShuntCompensator/rdf:type ?typeall .
#?nscpointsall cim:NonlinearShuntCompensatorPoint.NonlinearShuntCompensator $this .
#?nscpointsall rdf:type ?typeall .
}
GROUP BY $this ?typesall
}
$this $PATH ?value .
FILTER (?value!=?typesall) .
}
  • Messages: ["The number of NonlinearShuntCompenstorPoint instances associated with a NonlinearShuntCompensator does not equal to ShuntCompensator.maximumSections."]

eq:ShuntCompensator.nomU-nominalVoltageDifference​

Path: rdf:type
Name: C:301:EQ:ShuntCompensator.nomU:nominalVoltageDifference
This should normally be within 10% of the voltage at which the capacitor is connected to the network.

Severity: sh:Warning

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Warning)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this cim:ShuntCompensator.nomU ?value .
$this cim:Equipment.EquipmentContainer/cim:VoltageLevel.BaseVoltage/cim:BaseVoltage.nominalVoltage ?nomv .

FILTER (?value<0.9*?nomv && ?value>1.1*?nomv) .
}
  • Messages: ["The value differs with more than 10% of the nominal voltage abtained via the containment to VoltageLevel."]

eq:NuclearGeneratingUnit​

Severity: sh:Violation

Targets:

  • targetClass: cim:NuclearGeneratingUnit

eq:OperationalLimitType​

Severity: sh:Violation

Targets:

  • targetClass: cim:OperationalLimitType

Nested Properties:

eq:OperationalLimitType.acceptableDuration-usage​

Path: cim:OperationalLimitType.acceptableDuration
Name: C:301:EQ:OperationalLimitType.acceptableDuration:usage
The attribute has meaning only if the flag isInfiniteDuration is set to false, hence it shall not be exchanged when isInfiniteDuration is set to true.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this $PATH ?value .
BIND(EXISTS{$this $PATH ?v } AS ?hasvalue).
$this cim:OperationalLimitType.isInfiniteDuration ?indur .
FILTER (?hasvalue=true && ?indur=true ) .
}
  • Messages: ["The attribute is present and .isInfiniteDuration is set to true."]

eq:OperationalLimitType.isInfiniteDuration-usage​

Path: cim:OperationalLimitType.acceptableDuration
Name: C:301:EQ:OperationalLimitType.isInfiniteDuration:usage
If false, the limit has definite duration which is defined by the attribute acceptableDuration.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
#OPTIONAL {$this $PATH ?value }.
$this $PATH ?value .
BIND(EXISTS{$this $PATH ?v} AS ?hasvalue).
$this cim:OperationalLimitType.isInfiniteDuration ?indur .
FILTER (?hasvalue=false && ?indur=false ) .
}
  • Messages: ["The attribute is not present when .isInfiniteDuration is set ot false."]

eq:PhaseTapChangerAsymmetrical​

Severity: sh:Violation

Targets:

  • targetClass: cim:PhaseTapChangerAsymmetrical

Nested Properties:

eq:PhaseTapChangerAsymmetrical.windingConnectionAngle-valueRange​

Path: cim:PhaseTapChangerAsymmetrical.windingConnectionAngle
Name: C:301:EQ:PhaseTapChangerAsymmetrical.windingConnectionAngle:valueRange
The attribute can only be multiples of 30 degrees. The allowed range is -150 degrees to 150 degrees excluding 0.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this $PATH ?value .
FILTER (contains(str(?value), ".") || (?value!=-150 && ?value!=-120 && ?value!=-90 && ?value!=-60 && ?value!=-30 && ?value!=150 && ?value!=120 && ?value!=90 && ?value!=60 && ?value!=30)) .
}
  • Messages: ["The value is not an integer, multiples of 30 degrees in the range of -150 degrees to 150 degrees excluding 0."]

eq:PhaseTapChangerNonLinear.xMin-valueRangePair​

Path: cim:PhaseTapChangerNonLinear.xMin
Name: C:301:EQ:PhaseTapChangerNonLinear.xMin:valueRangePair
PowerTransformerEnd.x shall be consistent with PhaseTapChangerLinear.xMin and PhaseTapChangerNonLinear.xMin. In case of inconsistency, PowerTransformerEnd.x shall be used.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this $PATH ?value .
$this cim:PhaseTapChanger.TransformerEnd/cim:PowerTransformerEnd.x ?x .
#$this cim:PhaseTapChanger.TransformerEnd ?theend .
#?theend cim:PowerTransformerEnd.x ?x .
FILTER (?value!=?x ) .
}
  • Messages: ["Inconsistency between PowerTransformerEnd.x and PhaseTapChangerNonLinear.xMin."]

eq:PhaseTapChangerLinear​

Severity: sh:Violation

Targets:

  • targetClass: cim:PhaseTapChangerLinear

Nested Properties:

eq:PhaseTapChangerLinear.xMin-valueRangePair​

Path: cim:PhaseTapChangerLinear.xMin
Name: C:301:EQ:PhaseTapChangerLinear.xMin:valueRangePair
PowerTransformerEnd.x shall be consistent with PhaseTapChangerLinear.xMin and PhaseTapChangerNonLinear.xMin. In case of inconsistency, PowerTransformerEnd.x shall be used.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this $PATH ?value .
$this cim:PhaseTapChanger.TransformerEnd/cim:PowerTransformerEnd.x ?x .
#$this cim:PhaseTapChanger.TransformerEnd ?theend .
#?theend cim:PowerTransformerEnd.x ?x .
FILTER (?value!=?x ) .
}
  • Messages: ["Inconsistency between PowerTransformerEnd.x and PhaseTapChangerLinear.xMin."]

eq:PhaseTapChangerSymmetrical​

Severity: sh:Violation

Targets:

  • targetClass: cim:PhaseTapChangerSymmetrical

Nested Properties:

eq:PhaseTapChangerNonLinear.xMin-valueRangePair​

Path: cim:PhaseTapChangerNonLinear.xMin
Name: C:301:EQ:PhaseTapChangerNonLinear.xMin:valueRangePair
PowerTransformerEnd.x shall be consistent with PhaseTapChangerLinear.xMin and PhaseTapChangerNonLinear.xMin. In case of inconsistency, PowerTransformerEnd.x shall be used.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this $PATH ?value .
$this cim:PhaseTapChanger.TransformerEnd/cim:PowerTransformerEnd.x ?x .
#$this cim:PhaseTapChanger.TransformerEnd ?theend .
#?theend cim:PowerTransformerEnd.x ?x .
FILTER (?value!=?x ) .
}
  • Messages: ["Inconsistency between PowerTransformerEnd.x and PhaseTapChangerNonLinear.xMin."]

eq:PhaseTapChangerTabular​

Severity: sh:Violation

Targets:

  • targetClass: cim:PhaseTapChangerTabular

eq:PowerElectronicsConnection​

Severity: sh:Violation

Targets:

  • targetClass: cim:PowerElectronicsConnection

eq:PowerTransformer​

Severity: sh:Violation

Targets:

  • targetClass: cim:PowerTransformer

Nested Properties:

eq:PowerTransformer-associationNotUsed​

Path: rdf:type
Name: C:301:EQ:PowerTransformer:associationNotUsed
The inherited association ConductingEquipment.BaseVoltage should not be used. The association from TransformerEnd to BaseVoltage should be used instead.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this cim:ConductingEquipment.BaseVoltage ?value .
BIND(EXISTS{$this cim:ConductingEquipment.BaseVoltage ?v } AS ?hasvalue).
FILTER (?hasvalue=true) .
}
  • Messages: ["The inherited association ConductingEquipment.BaseVoltage is used."]

eq:PowerTransformerEnd.ratedS-valueRange2winding​

Path: rdf:type
Name: C:301:EQ:PowerTransformerEnd.ratedS:valueRange2winding
For a two-winding transformer the values for the high and low voltage sides shall be identical.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value ?ends
WHERE {
{
SELECT $this (COUNT(?typeend) AS ?ends)
WHERE {
$this ^cim:PowerTransformerEnd.PowerTransformer/rdf:type ?typeend .
}
GROUP BY $this ?typeend
}

?end1 cim:PowerTransformerEnd.PowerTransformer $this .
?end1 cim:TransformerEnd.endNumber 1.
?end1 cim:PowerTransformerEnd.ratedS ?value .
#OPTIONAL {?end1 cim:PowerTransformerEnd.ratedS ?value }.
BIND(EXISTS{?end1 cim:PowerTransformerEnd.ratedS ?v} AS ?hasvalue).
?end2 cim:PowerTransformerEnd.PowerTransformer $this .
?end2 cim:TransformerEnd.endNumber 2 .
?end2 cim:PowerTransformerEnd.ratedS ?ratedsend2 .
BIND(EXISTS{?end2 cim:PowerTransformerEnd.ratedS ?r} AS ?hasratedsend2).
#OPTIONAL {?end2 cim:PowerTransformerEnd.ratedS ?ratedsend2 }.

FILTER (?hasvalue=true && ?hasratedsend2=true && ?end1!=?end2 && ?value!=?ratedsend2) .
}
HAVING(?ends=2)

  • Messages: ["The value is different for a two-winding transformer."]

eq:PowerTransformerEnd.ratedU-valueRange​

Path: rdf:type
Name: C:301:EQ:PowerTransformerEnd.ratedU:valueRange
A high voltage side, as given by TransformerEnd.endNumber, shall have a ratedU that is greater than or equal to ratedU for the lower voltage sides. The attribute shall be a positive value.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value ?ends
WHERE {
{
SELECT $this (COUNT(?typeend) AS ?ends)
WHERE {
$this ^cim:PowerTransformerEnd.PowerTransformer/rdf:type ?typeend .
}
GROUP BY $this ?typeend
}

?end1 cim:PowerTransformerEnd.PowerTransformer $this .
?end1 cim:TransformerEnd.endNumber 1.
?end1 cim:PowerTransformerEnd.ratedU ?value .
?end2 cim:PowerTransformerEnd.PowerTransformer $this .
?end2 cim:TransformerEnd.endNumber 2 .
?end2 cim:PowerTransformerEnd.ratedU ?rateduend2 .
#BIND(EXISTS{$this cim:PowerTransformerEnd.PowerTransformer/cim:TransformerEnd.endNumber 3} AS ?isthreew).
#?end3 cim:PowerTransformerEnd.PowerTransformer $this .
#?end3 cim:TransformerEnd.endNumber 3 .
#?end3 cim:PowerTransformerEnd.ratedU ?rateduend3 .
OPTIONAL {?end3 cim:PowerTransformerEnd.PowerTransformer $this } .
OPTIONAL {?end3 cim:TransformerEnd.endNumber 3 }.
OPTIONAL {?end3 cim:PowerTransformerEnd.ratedU ?rateduend3 }.

FILTER (((?value<?rateduend2 || ?value<=0 || ?rateduend2<=0) && ?ends=2 && ?end1!=?end2 && ?end3=?end1) || (?ends=3 && ?end1!=?end2 && ?end1!=?end3 && ?end2!=?end3 && (?value<?rateduend2 || ?rateduend2<?rateduend3 || ?value<=0 || ?rateduend2<=0 || ?rateduend3<=0))) .
}


  • Messages: ["The PowerTransformerEnd.ratedU does not fuifil one of the following: 1) it is not a positive value; 2) the value of the high voltage side shall be greater than or equal to ratedU for the lower voltage sides."]

eq:TransformerEnd.endNumber-unique​

Path: rdf:type
Name: C:301:EQ:TransformerEnd.endNumber:unique
Highest voltage winding should be 1. Each end within a power transformer should have a unique subsequent end number.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
{
SELECT $this (COUNT(DISTINCT ?endnumber) as ?countd) (COUNT(?endnumber) as ?count) (MIN(?endnumber) as ?minendnumber) (MAX(?ratedu) as ?maxratedu)
WHERE {
$this ^cim:PowerTransformerEnd.PowerTransformer ?ends .
?ends rdf:type ?endtype .
?ends cim:TransformerEnd.endNumber ?endnumber .
?ends cim:PowerTransformerEnd.ratedU ?ratedu .
}
GROUP BY $this ?endtype
}

?end1 cim:PowerTransformerEnd.PowerTransformer $this .
?end1 cim:TransformerEnd.endNumber ?minendnumber.
?end1 cim:PowerTransformerEnd.ratedU ?end1ratedu .

?end2 cim:PowerTransformerEnd.PowerTransformer $this .
?end2 cim:PowerTransformerEnd.ratedU ?maxratedu .
BIND("" as ?value).
FILTER(?countd!=?count || (?countd=?count && ?end1ratedu!=?maxratedu && ?end1!=?end2) ).
}

  • Messages: ["The PowerTransformer has TransformerEnd.endNumber which is not unique or the PowerTransformerEnd with endNumber 1 is not the highest voltage winding."]

eq:PowerTransformer-twoWinding​

Severity: sh:Violation

Targets:

  • sparqlTarget:

Nested Properties:

eq:PowerTransformerEnd-secondWindingValues​

Path: rdf:type
Name: C:301:EQ:PowerTransformerEnd:secondWindingValues

  1. for a two Terminal PowerTransformer the high voltage (TransformerEnd.endNumber=1) PowerTransformerEnd has non zero values on r, r0, x, and x0 while the low voltage (TransformerEnd.endNumber=2) PowerTransformerEnd has zero values for r, r0, x, and x0. Parameters are always provided, even if the PowerTransformerEnds have the same rated voltage. In this case, the parameters are provided at the PowerTransformerEnd which has TransformerEnd.endNumber equal to 1.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
?value cim:PowerTransformerEnd.PowerTransformer $this .
?value cim:TransformerEnd.endNumber 2 .
#?value cim:TransformerEnd.endNumber ?endnumber .
?value cim:PowerTransformerEnd.r ?r .
?value cim:PowerTransformerEnd.r0 ?r0 .
?value cim:PowerTransformerEnd.x ?x .
?value cim:PowerTransformerEnd.x0 ?x0 .
FILTER (!(?r=0 && ?r0=0 && ?x=0 && ?x0=0)).
#FILTER ((!(?r=0 && ?r0=0 && ?x=0 && ?x0=0) && ?endnumber=2) || (!(?r!=0 && ?r0!=0 && ?x!=0 && ?x0!=0) && ?endnumber=1)).
#FILTER (?r!=0 || ?r0!=0 || ?x!=0 || ?x0!=0).
}
  • Messages: ["Non-zero values for the PowerTransformerEnd with TransformerEnd.endNumber=2 for a two Terminal PowerTransformer."]

eq:PowerTransformerEnd​

Severity: sh:Violation

Targets:

  • targetClass: cim:PowerTransformerEnd

Nested Properties:

eq:PowerTransformerEnd.r-valueRange​

Path: cim:PowerTransformerEnd.r
Name: C:301:EQ:PowerTransformerEnd.r:valueRange
The attribute shall be equal to or greater than zero for non-equivalent transformers.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this $PATH ?value .
OPTIONAL {$this cim:Equipment.aggregate ?aggregate }.
#BIND(EXISTS{$this cim:Equipment.aggregate ?a } AS ?hasaggregate).
FILTER ((!bound(?aggregate) || ?aggregate=false) && ?value<0 ) .
}
  • Messages: ["The value is negative for a non-equivalent transformer."]

eq:PowerTransformerEnd-terminalConsistency​

Path: rdf:type
Name: C:301:EQ:PowerTransformerEnd:terminalConsistency
In all cases a PowerTransformer models a group of physical devices acting together to transform power among terminals and in one physical location.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this
WHERE {
$this cim:TransformerEnd.Terminal/cim:Terminal.ConductingEquipment ?endtermpt .
$this cim:PowerTransformerEnd.PowerTransformer ?pendpt .

FILTER (?endtermpt!=?pendpt) .
}
  • Messages: ["The Terminal referenced by TransformerEnd.Terminal points to a PowerTransformer which is different than the referenced element via PowerTransformerEnd.PowerTransformer."]

eq:RatioTapChanger​

Severity: sh:Violation

Targets:

  • targetClass: cim:RatioTapChanger

eq:ReactiveCapabilityCurve-curveYvalues​

Name: C:301:EQ:ReactiveCapabilityCurve:yvalues
For each active power value there is a corresponding high and low reactive power limit value. Typically there will be a separate curve for each coolant condition, such as hydrogen pressure.

Severity: sh:Violation

Messages:

  • "CurveData associated with a ReactiveCapabilityCurve does not have both .y1value and .y2value defined."

Targets:

  • targetClass: cim:CurveData

eq:RegularTimePoint​

Severity: sh:Violation

Targets:

  • targetClass: cim:RegularTimePoint

eq:RegulatingControl​

Severity: sh:Violation

Targets:

  • targetClass: cim:RegulatingControl

Nested Properties:

eq:RegulatingControl-terminalConnectivityNode​

Path: cim:RegulatingControl.Terminal
Name: C:301:EQ:RegulatingControl:terminalConnectivityNode
The specified terminal shall be associated with the connectivity node of the controlled point. The most specific subtype of RegulatingControl shall be used in case such equipment participate in the control, e.g. TapChangerControl for tap changers.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this $PATH ?value .
BIND(EXISTS{?value cim:Terminal.ConnectivityNode ?cn} AS ?hascn).
#OPTIONAL {?value cim:Terminal.ConnectivityNode ?cn }.
FILTER (?hascn=false) .
}
  • Messages: ["The Terminal referenced by the RegulatingControl is not associated with a ConnectivityNode."]

eq:SeriesCompensator​

Severity: sh:Violation

Targets:

  • targetClass: cim:SeriesCompensator

eq:SolarGeneratingUnit​

Severity: sh:Violation

Targets:

  • targetClass: cim:SolarGeneratingUnit

eq:StaticVarCompensator​

Severity: sh:Violation

Targets:

  • targetClass: cim:StaticVarCompensator

eq:Switch​

Severity: sh:Violation

Targets:

  • targetClass: cim:Switch

eq:SynchronousMachine​

Severity: sh:Violation

Targets:

  • targetClass: cim:SynchronousMachine

eq:TapChanger​

Severity: sh:Violation

Targets:

  • targetClass: cim:PhaseTapChangerSymmetrical
  • targetClass: cim:PhaseTapChangerAsymmetrical
  • targetClass: cim:PhaseTapChangerLinear
  • targetClass: cim:RatioTapChanger
  • targetClass: cim:PhaseTapChangerTabular

Nested Properties:

eq:TapChanger.ltcFlag-tapChangerControl​

Path: cim:TapChanger.ltcFlag
Name: C:301:EQ:TapChanger.ltcFlag:tapChangerControl
When TapChanger.ltcFlag=false and TapChanger.TapChangerControl is present an artificial tap changer can be used to simulate control behaviour in power flow.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this $PATH ?value .
BIND(EXISTS{$this cim:TapChanger.TapChangerControl ?tcc } AS ?hastcc).

FILTER (?hastcc=true && ?value=false) .
}
  • Messages: ["An artificial tap changer is used to simulate control behaviour in power flow."]

eq:DCConverterUnit-tapChangerControl​

Path: rdf:type
Name: C:301:EQ:DCConverterUnit:tapChangerControl
No TapChangerControl is used for the converter transformer, the control function is described in the ACDCConverter-s.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
OPTIONAL {$this cim:TapChanger.TapChangerControl ?value }.
OPTIONAL {$this cim:RatioTapChanger.TransformerEnd/cim:PowerTransformerEnd.PowerTransformer/cim:Equipment.EquipmentContainer/rdf:type ?typeratiotc }.
OPTIONAL {$this cim:PhaseTapChanger.TransformerEnd/cim:PowerTransformerEnd.PowerTransformer/cim:Equipment.EquipmentContainer/rdf:type ?typephasetc }.

FILTER (bound(?value) && ((bound(?typeratiotc) && ?typeratiotc=cim:DCConverterUnit) || (bound(?typephasetc) && ?typephasetc=cim:DCConverterUnit))) .
}
  • Messages: ["TapChangerControl is association to a transformer contained in DCConverterUnit."]

eq:TapChangerControl​

Severity: sh:Violation

Targets:

  • targetClass: cim:TapChangerControl

Nested Properties:

eq:RegulatingControl-terminalConnectivityNode​

Path: cim:RegulatingControl.Terminal
Name: C:301:EQ:RegulatingControl:terminalConnectivityNode
The specified terminal shall be associated with the connectivity node of the controlled point. The most specific subtype of RegulatingControl shall be used in case such equipment participate in the control, e.g. TapChangerControl for tap changers.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this $PATH ?value .
BIND(EXISTS{?value cim:Terminal.ConnectivityNode ?cn} AS ?hascn).
#OPTIONAL {?value cim:Terminal.ConnectivityNode ?cn }.
FILTER (?hascn=false) .
}
  • Messages: ["The Terminal referenced by the RegulatingControl is not associated with a ConnectivityNode."]

eq:Terminal​

Severity: sh:Violation

Targets:

  • targetClass: cim:GroundingImpedance
  • targetClass: cim:PetersenCoil
  • targetClass: cim:GroundDisconnector
  • targetClass: cim:Ground

eq:Terminal.phases​

Severity: sh:Violation

Targets:

  • targetClass: cim:ConnectivityNode

Nested Properties:

eq:Terminal.phases-consistencyConnectivityNode​

Path: rdf:type
Name: C:301:EQ:Terminal.phases:consistencyConnectivityNode
The phase code on terminals connecting same ConnectivityNode or same TopologicalNode as well as for equipment between two terminals shall be consistent.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value2 ?terms ?value1 ?value
WHERE {
{
SELECT $this (COUNT(?typeterm) AS ?terms) ?value
WHERE {
$this ^cim:Terminal.ConnectivityNode ?value .
?value rdf:type ?typeterm .
#?term cim:Terminal.ConnectivityNode $this .
#?term rdf:type ?typeterm .
}
GROUP BY $this ?typeterm ?value
HAVING (?terms>1)
}

#$this ^cim:Terminal.ConnectivityNode ?value .
$this ^cim:Terminal.ConnectivityNode ?term2 .
?value cim:Terminal.phases ?value1 .
OPTIONAL {?term2 cim:Terminal.phases ?value2 } .

#?value cim:Terminal.ConnectivityNode $this .
#?term1 cim:Terminal.phases ?value1 .
#?term2 cim:Terminal.ConnectivityNode $this .
#?term2 cim:Terminal.phases ?value2.

#BIND(EXISTS{?term1 cim:Terminal.phases ?v1} AS ?hasvalue1).


#BIND(EXISTS{?term2 cim:Terminal.phases ?v2} AS ?hasvalue2).
#FILTER ((?terms>1 && ?hasvalue2=true && ?hasvalue1=true && ?term1!=?term2 && (?value1=cim:PhaseCode.ABCN || ?value1=cim:PhaseCode.N) && (?value2!=cim:PhaseCode.ABCN && ?value2!=cim:PhaseCode.N)) ||
#(?terms>1 && ?hasvalue2=true && ?hasvalue1=true && ?term1!=?term2 && (?value1=cim:PhaseCode.ABC) && (?value2!=cim:PhaseCode.ABC)) ||
#(?terms>1 && ?hasvalue1=true && ?hasvalue2=false && ?term1!=?term2 && (?value1=cim:PhaseCode.ABCN || ?value1=cim:PhaseCode.N))
#) .
FILTER ((?value!=?term2 && bound(?value2) && (?value1=cim:PhaseCode.ABCN || ?value1=cim:PhaseCode.N) && (?value2!=cim:PhaseCode.ABCN && ?value2!=cim:PhaseCode.N)) ||
(?value!=?term2 && bound(?value2) && (?value1=cim:PhaseCode.ABC) && (?value2!=cim:PhaseCode.ABC)) ||
(?value!=?term2 && !bound(?value2) && (?value1=cim:PhaseCode.ABCN || ?value1=cim:PhaseCode.N))
) .
}
  • Messages: ["The phase codes for the connected terminals are not consistent. Terminal 1 code:{?value1} Terminal 2 code: {?value2}."]

eq:ThermalGeneratingUnit​

Severity: sh:Violation

Targets:

  • targetClass: cim:ThermalGeneratingUnit

eq:VoltageLimit​

Severity: sh:Violation

Targets:

  • targetClass: cim:VoltageLimit

Nested Properties:

eq:LimitKind.patl-allowedType​

Path: rdf:type
Name: C:301:EQ:LimitKind.patl:allowedType
The Permanent Admissible Transmission Loading (PATL) is the loading in amperes, MVA or MW that can be accepted by a network branch for an unlimited duration without any risk for the material.

Severity: sh:Violation

Constraints:

  • sh:SPARQLConstraintComponent (Severity: sh:Violation)
PREFIX cim: <http://iec.ch/TC57/CIM100#>
PREFIX rdf: <http://www.w3.org/1999/02/22-rdf-syntax-ns#>
PREFIX eu: <http://iec.ch/TC57/CIM100-European#>

SELECT $this ?value
WHERE {
$this cim:OperationalLimit.OperationalLimitType/eu:OperationalLimitType.kind ?value.
#?type eu:OperationalLimitType.kind ?value .

FILTER (?value=eu:LimitKind.patl) .
}
  • Messages: ["PATL type is provided for VoltageLimit."]

eq:VsConverter​

Severity: sh:Violation

Targets:

  • targetClass: cim:VsConverter

eq:WindGeneratingUnit​

Severity: sh:Violation

Targets:

  • targetClass: cim:WindGeneratingUnit