61970-452_Equipment-AP-Con-Complex-SHACL

eq452c:ACDCConverter​

Severity: sh:Violation

Targets:

  • targetClass: cim:CsConverter
  • targetClass: cim:VsConverter

Nested Properties:

eq452c:DCConverterUnit.Substation-containment​

Path: cim:Equipment.EquipmentContainer / cim:DCConverterUnit.Substation / rdf:type
Name: C:452:EQ:ACDCConverter:containment
For ACDCConverter (CsConverter, VsConverter) the association Equipment.EquipmentContainer is required and shall point to DCEquipmentContainer of type DCConverterUnit. In this case the association DCConverterUnit.Substation is required.

Severity: sh:Violation

Messages:

  • "The DCConverterUnit.Substation association is either missing or not pointing to a Substation."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Substation]

eq452c:ACDCConverter-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:ACDCConverter:containment
For ACDCConverter (CsConverter, VsConverter) the association Equipment.EquipmentContainer is required and shall point to DCEquipmentContainer of type DCConverterUnit. In this case the association DCConverterUnit.Substation is required.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not DCConverterUnit."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:DCConverterUnit]

eq452c:ACLineSegment​

Severity: sh:Violation

Targets:

  • targetClass: cim:ACLineSegment

Nested Properties:

eq452c:ACLineSegment.r-valueRange​

Path: cim:ACLineSegment.r
Name: C:452:EQ:ACLineSegment.r:valueRange
ACLineSegment.r shall be a positive value or zero.

Severity: sh:Violation

Messages:

  • "The value is negative."

Constraints:

  • sh:MinInclusiveConstraintComponent (Severity: sh:Violation)
    • Value: 0.0

eq452c:ACLineSegment.x-valueRange​

Path: cim:ACLineSegment.x
Name: C:452:EQ:ACLineSegment.x:valueRange
The attribute shall be a positive value. As negative reactance values are not allowed for ACLineSegment-s it is recommended to model series compensators explicitly.

Severity: sh:Violation

Messages:

  • "The value is negative or zero."

Constraints:

  • sh:MinExclusiveConstraintComponent (Severity: sh:Violation)
    • Value: 0.0

eq452c:ConductingEquipment.BaseVoltage-whereRequired​

Path: cim:ConductingEquipment.BaseVoltage
Name: C:452:EQ:ConductingEquipment.BaseVoltage:whereRequired
The ConductingEquipment.BaseVoltage association is required for the following ConductingEquipment: ACLineSegment, EquivalentBranch and SeriesCompensator. For all other Equipment-s, not contained in a VoltageLevel, the association ConductingEquipment.BaseVoltage can be provided (as it is optional), however the association to BaseVoltage coming from the container or transformer ends takes precedence.

Severity: sh:Violation

Messages:

  • "The association ConductingEquipment.BaseVoltage is not provided."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1

eq452c:AuxiliaryEquipment​

Severity: sh:Violation

Targets:

  • targetClass: cim:WaveTrap
  • targetClass: cim:FaultIndicator
  • targetClass: cim:CurrentTransformer
  • targetClass: cim:PotentialTransformer
  • targetClass: cim:PostLineSensor
  • targetClass: cim:SurgeArrester

Nested Properties:

eq452c:AuxiliaryEquipment-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:AuxilaryEquipment:containment
For AuxilaryEquipment (CurrentTransformer, PotentialTransformer, PostLineSensor, SurgeArrester, WaveTrap, FaultIndicator) the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type Bay or Line.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not Bay or Line."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Bay cim:Line]

eq452c:Breaker​

Severity: sh:Violation

Targets:

  • targetClass: cim:Breaker

eq452c:BusbarSection​

Severity: sh:Violation

Targets:

  • targetClass: cim:BusbarSection

Nested Properties:

eq452c:BusbarSection-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:BusbarSection:containment
For BusbarSection the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type VoltageLevel or Bay (when a disconnector is splitting a busbar section in two).

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not Bay or VoltageLevel."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Bay cim:VoltageLevel]

eq452c:Clamp​

Severity: sh:Violation

Targets:

  • targetClass: cim:Clamp

Nested Properties:

eq452c:Clamp-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:Clamp:containment
For Clamp the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type Bay or Line when outside substation.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not Bay or Line."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Bay cim:Line]

eq452c:ConductingEquipment-twoTerminalsShape​

Severity: sh:Violation

Targets:

  • targetClass: cim:LoadBreakSwitch
  • targetClass: cim:SeriesCompensator
  • targetClass: cim:DCSwitch
  • targetClass: cim:DCChopper
  • targetClass: cim:Fuse
  • targetClass: cim:GroundDisconnector
  • targetClass: cim:Jumper
  • targetClass: cim:Breaker
  • targetClass: cim:Cut
  • targetClass: cim:ACLineSegment
  • targetClass: cim:DCBreaker
  • targetClass: cim:Disconnector
  • targetClass: cim:DisconnectingCircuitBreaker
  • targetClass: cim:EquivalentBranch
  • targetClass: cim:DCLineSegment
  • targetClass: cim:DCSeriesDevice
  • targetClass: cim:DCDisconnector
  • targetClass: cim:Switch

eq452c:Conductor​

Severity: sh:Violation

Targets:

  • targetClass: cim:ACLineSegment

Nested Properties:

eq452c:Conductor-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:Conductor:containment
For Conductor (ACLineSegment) the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type Line.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not Line."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Line]

eq452c:CurveData​

Severity: sh:Violation

Targets:

  • targetClass: cim:CurveData

eq452c:Cut​

Severity: sh:Violation

Targets:

  • targetClass: cim:Cut

Nested Properties:

eq452c:Cut-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:Cut:containment
For Cut the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type Bay, VoltageLevel or DCConverterUnit or Line when outside substation.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not Bay, VoltageLevel, DCConverterUnit or Line."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Bay cim:VoltageLevel cim:DCConverterUnit cim:Line]

eq452c:DCBusbar​

Severity: sh:Violation

Targets:

  • targetClass: cim:DCBusbar

Nested Properties:

eq452c:DCBusbar-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:DCBusbar:containment
For DCBusbar the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type DCConverterUnit.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not DCConverterUnit."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:DCConverterUnit]

eq452c:DCChopper​

Severity: sh:Violation

Targets:

  • targetClass: cim:DCChopper

Nested Properties:

eq452c:DCChopper-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:DCChopper:containment
For DCChopper the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type DCConverterUnit.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not DCConverterUnit."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:DCConverterUnit]

eq452c:DCGround​

Severity: sh:Violation

Targets:

  • targetClass: cim:DCGround

Nested Properties:

eq452c:DCGround-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:DCGround:containment
For DCGround the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type DCConverterUnit.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not DCConverterUnit."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:DCConverterUnit]

eq452c:DCLineSegment​

Severity: sh:Violation

Targets:

  • targetClass: cim:DCLineSegment

Nested Properties:

eq452c:DCLineSegment.resistance-valueRange​

Path: cim:DCLineSegment.resistance
Name: C:452:EQ:DCLineSegment.resistance:valueRange
The attribute DCLineSegment.resistance shall be a positive value.

Severity: sh:Violation

Messages:

  • "The value is negative or zero."

Constraints:

  • sh:MinExclusiveConstraintComponent (Severity: sh:Violation)
    • Value: 0.0

eq452c:DCLineSegment-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:DCLineSegment:containment
For DCLineSegment the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type DCLine. In the case of modelling back to back configuration the association shall point to EquipmentContainer of type Substation.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not DCLine or Substation."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:DCLine cim:Substation]

eq452c:DCSeriesDevice​

Severity: sh:Violation

Targets:

  • targetClass: cim:DCSeriesDevice

Nested Properties:

eq452c:DCSeriesDevice-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:DCSeriesDevice:containment
For DCSeriesDevice the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type DCConverterUnit.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not DCConverterUnit."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:DCConverterUnit]

eq452c:DCShunt​

Severity: sh:Violation

Targets:

  • targetClass: cim:DCShunt

Nested Properties:

eq452c:DCShunt-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:DCShunt:containment
For DCShunt the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type DCConverterUnit.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not DCConverterUnit."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:DCConverterUnit]

eq452c:DCSwitch​

Severity: sh:Violation

Targets:

  • targetClass: cim:DCDisconnector
  • targetClass: cim:DCBreaker

Nested Properties:

eq452c:DCSwitch-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:DCSwitch:containment
For DCSwitch (DCDisconnector, DCBreaker) the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type DCConverterUnit.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not DCConverterUnit."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:DCConverterUnit]

eq452c:DayType​

Severity: sh:Violation

Targets:

  • targetClass: cim:DayType

Nested Properties:

eq452c:IdentifiedObject.name-validValues​

Path: cim:IdentifiedObject.name
Name: C:452:EQ:DayType.name:validValues
For DayType the name attribute indicates the days of the week that a given DayType represents. The name attribute is restricted to the following names: Monday, Tuesday, Wednesday, Thursday, Friday, Saturday, Sunday, Weekday, Weekend, All. If the name attribute is All, it represents all seven days of the week. If the name attribute is Weekday, it represents Monday through Friday. If the name attribute is Weekend, it represents Saturday and Sunday.

Severity: sh:Violation

Messages:

  • "Not valid value. The value is not one of the following values: Monday, Tuesday, Wednesday, Thursday, Friday, Saturday, Sunday, Weekday, Weekend, All."

Constraints:

  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [Monday Tuesday Wednesday Thursday Friday Saturday Sunday Weekday Weekend All]

eq452c:DisconnectingCircuitBreaker​

Severity: sh:Violation

Targets:

  • targetClass: cim:DisconnectingCircuitBreaker

eq452c:Disconnector​

Severity: sh:Violation

Targets:

  • targetClass: cim:Disconnector

Nested Properties:

eq452c:Disconnector-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:Disconnector:containment
For Disconnector the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type Bay, VoltageLevel, DCConverterUnit or Line when outside substation.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not Bay, VoltageLevel, DCConverterUnit or Line."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Bay cim:VoltageLevel cim:DCConverterUnit cim:Line]

eq452c:EarthFaultCompensator​

Severity: sh:Violation

Targets:

  • targetClass: cim:GroundingImpedance
  • targetClass: cim:PetersenCoil

Nested Properties:

eq452c:EarthFaultCompensator-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:EarthFaultCompensator:containment
For EarthFaultCompensator (GroundingImpedance, PetersenCoil) the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type VoltageLevel.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not VoltageLevel."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:VoltageLevel]

eq452c:EnergyConnection​

Severity: sh:Violation

Targets:

  • targetClass: cim:EnergySource
  • targetClass: cim:LinearShuntCompensator
  • targetClass: cim:StaticVarCompensator
  • targetClass: cim:SynchronousMachine
  • targetClass: cim:EnergyConsumer
  • targetClass: cim:NonConformLoad
  • targetClass: cim:ConformLoad
  • targetClass: cim:NonlinearShuntCompensator
  • targetClass: cim:ExternalNetworkInjection
  • targetClass: cim:AsynchronousMachine

Nested Properties:

eq452c:EnergyConnection-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:EnergyConnection:containment
For EnergyConnection (EnergySource, EnergyConsumer, NonConformLoad, ConformLoad, LinearShuntCompensator, NonlinearShuntCompensator, ExternalNetworkInjection, StaticVarCompensator, SynchronousMachine, AsynchronousMachine) the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type VoltageLevel.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not VoltageLevel."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:VoltageLevel]

eq452c:EquivalentBranch​

Severity: sh:Violation

Targets:

  • targetClass: cim:EquivalentBranch

Nested Properties:

eq452c:ConductingEquipment.BaseVoltage-whereRequired​

Path: cim:ConductingEquipment.BaseVoltage
Name: C:452:EQ:ConductingEquipment.BaseVoltage:whereRequired
The ConductingEquipment.BaseVoltage association is required for the following ConductingEquipment: ACLineSegment, EquivalentBranch and SeriesCompensator. For all other Equipment-s, not contained in a VoltageLevel, the association ConductingEquipment.BaseVoltage can be provided (as it is optional), however the association to BaseVoltage coming from the container or transformer ends takes precedence.

Severity: sh:Violation

Messages:

  • "The association ConductingEquipment.BaseVoltage is not provided."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1

eq452c:EquivalentBranch-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:EquivalentBranch:containment
For EquivalentBranch the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type VoltageLevel, Line or Substation.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not VoltageLevel, Line or Substation."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:VoltageLevel cim:Line cim:Substation]

eq452c:EquivalentInjection​

Severity: sh:Violation

Targets:

  • targetClass: cim:EquivalentInjection

Nested Properties:

eq452c:EquivalentInjection-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:EquivalentInjection:containment
For EquivalentInjection the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type VoltageLevel or Line.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not VoltageLevel or Line."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:VoltageLevel cim:Line]

eq452c:EquivalentShunt​

Severity: sh:Violation

Targets:

  • targetClass: cim:EquivalentShunt

Nested Properties:

eq452c:EquivalentShunt-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:EquivalentShunt:containment
For EquivalentShunt the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type VoltageLevel.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not VoltageLevel."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:VoltageLevel]

eq452c:Fuse​

Severity: sh:Violation

Targets:

  • targetClass: cim:Fuse

Nested Properties:

eq452c:Fuse-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:Fuse:containment
For Fuse the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type Bay, VoltageLevel, DCConverterUnit or Line when outside substation.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not Bay, VoltageLevel, DCConverterUnit or Line."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Bay cim:VoltageLevel cim:DCConverterUnit cim:Line]

eq452c:GeneratingUnit​

Severity: sh:Violation

Targets:

  • targetClass: cim:GeneratingUnit

Nested Properties:

eq452c:GeneratingUnit.minOperatingP-valueRangePair​

Path: cim:GeneratingUnit.minOperatingP
Name: C:452:EQ:GeneratingUnit.minOperatingP:valueRangePair
GeneratingUnit.maxOperatingP shall be greater than or equal to GeneratingUnit.minOperatingP.

Severity: sh:Violation

Messages:

  • "The value is greater than the value of GeneratingUnit.maxOperatingP."

Constraints:

  • sh:LessThanOrEqualsConstraintComponent (Severity: sh:Violation)
    • Path: cim:GeneratingUnit.maxOperatingP

eq452c:GeneratingUnit-containmentNodeShape​

Severity: sh:Violation

Targets:

  • targetClass: cim:ThermalGeneratingUnit
  • targetClass: cim:HydroGeneratingUnit
  • targetClass: cim:WindGeneratingUnit
  • targetClass: cim:GeneratingUnit
  • targetClass: cim:SolarGeneratingUnit
  • targetClass: cim:NuclearGeneratingUnit

Nested Properties:

eq452c:GeneratingUnit-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:GeneratingUnit:containment
For GeneratingUnit (SolarGeneratingUnit, NuclearGeneratingUnit, ThermalGeneratingUnit, HydroGeneratingUnit, WindGeneratingUnit) the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type Substation.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not Substation."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Substation]

eq452c:GeneratingUnit.aggregate​

Severity: sh:Violation

Targets:

  • targetClass: cim:GeneratingUnit
  • targetClass: cim:SolarGeneratingUnit
  • targetClass: cim:HydroGeneratingUnit
  • targetClass: cim:WindGeneratingUnit
  • targetClass: cim:ThermalGeneratingUnit
  • targetClass: cim:NuclearGeneratingUnit

eq452c:Ground​

Severity: sh:Violation

Targets:

  • targetClass: cim:Ground

Nested Properties:

eq452c:Ground-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:Ground:containment
For Ground the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type Bay or VoltageLevel.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not Bay or VoltageLevel."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Bay cim:VoltageLevel]

eq452c:GroundDisconnector​

Severity: sh:Violation

Targets:

  • targetClass: cim:GroundDisconnector

Nested Properties:

eq452c:GroundDisconnector-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:GroundDisconnector:containment
For GroundDisconnector the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type Bay, VoltageLevel, DCConverterUnit or Line when outside substation.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not Bay, VoltageLevel, DCConverterUnit or Line."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Bay cim:VoltageLevel cim:DCConverterUnit cim:Line]

eq452c:HydroGeneratingUnit​

Severity: sh:Violation

Targets:

  • targetClass: cim:HydroGeneratingUnit

Nested Properties:

eq452c:GeneratingUnit.minOperatingP-valueRangePair​

Path: cim:GeneratingUnit.minOperatingP
Name: C:452:EQ:GeneratingUnit.minOperatingP:valueRangePair
GeneratingUnit.maxOperatingP shall be greater than or equal to GeneratingUnit.minOperatingP.

Severity: sh:Violation

Messages:

  • "The value is greater than the value of GeneratingUnit.maxOperatingP."

Constraints:

  • sh:LessThanOrEqualsConstraintComponent (Severity: sh:Violation)
    • Path: cim:GeneratingUnit.maxOperatingP

eq452c:HydroPump​

Severity: sh:Violation

Targets:

  • targetClass: cim:HydroPump

Nested Properties:

eq452c:HydroPump-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:HydroPump:containment
For HydroPump the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type Substation.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not Substation."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Substation]

eq452c:Jumper​

Severity: sh:Violation

Targets:

  • targetClass: cim:Jumper

Nested Properties:

eq452c:Jumper-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:Jumper:containment
For Jumper the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type Bay, VoltageLevel, DCConverterUnit or Line when outside substation.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not Bay, VoltageLevel, DCConverterUnit or Line."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Bay cim:VoltageLevel cim:DCConverterUnit cim:Line]

eq452c:Junction​

Severity: sh:Violation

Targets:

  • targetClass: cim:Junction

Nested Properties:

eq452c:Junction-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:Junction:containment
For Junction the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type Line (in case they model T-junction of a Line), or VoltageLevel or Bay (in case they model named join locations within a Substation).

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not Line, Bay or VoltageLevel."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Line cim:Bay cim:VoltageLevel]

eq452c:LinearShuntCompensator​

Severity: sh:Violation

Targets:

  • targetClass: cim:LinearShuntCompensator

Nested Properties:

eq452c:LinearShuntCompensator.gPerSection-valueRange​

Path: cim:LinearShuntCompensator.gPerSection
Name: C:452:EQ:LinearShuntCompensator.gPerSection:valueRange
LinearShuntCompensator.gPerSection shall be a positive value or zero.

Severity: sh:Violation

Messages:

  • "The value is negative."

Constraints:

  • sh:MinInclusiveConstraintComponent (Severity: sh:Violation)
    • Value: 0.0

eq452c:ShuntCompensator.voltageSensitivity-valueRange​

Path: cim:ShuntCompensator.voltageSensitivity
Name: C:452:EQ:ShuntCompensator.voltageSensitivity:valueRange
The ShuntCompensator.voltageSensitivity attribute shall be greater than zero.

Severity: sh:Violation

Messages:

  • "The value is negative or zero."

Constraints:

  • sh:MinExclusiveConstraintComponent (Severity: sh:Violation)
    • Value: 0.0

eq452c:LoadBreakSwitch​

Severity: sh:Violation

Targets:

  • targetClass: cim:LoadBreakSwitch

eq452c:NonlinearShuntCompensator​

Severity: sh:Violation

Targets:

  • targetClass: cim:NonlinearShuntCompensator

Nested Properties:

eq452c:ShuntCompensator.voltageSensitivity-valueRange​

Path: cim:ShuntCompensator.voltageSensitivity
Name: C:452:EQ:ShuntCompensator.voltageSensitivity:valueRange
The ShuntCompensator.voltageSensitivity attribute shall be greater than zero.

Severity: sh:Violation

Messages:

  • "The value is negative or zero."

Constraints:

  • sh:MinExclusiveConstraintComponent (Severity: sh:Violation)
    • Value: 0.0

eq452c:NonlinearShuntCompensatorPoint​

Severity: sh:Violation

Targets:

  • targetClass: cim:NonlinearShuntCompensatorPoint

Nested Properties:

eq452c:NonlinearShuntCompensatorPoint.g-valueRange​

Path: cim:NonlinearShuntCompensatorPoint.g
Name: C:452:EQ:NonlinearShuntCompensatorPoint.g:valueRange
NonlinearShuntCompensatorPoint.g shall be a positive value or zero.

Severity: sh:Violation

Messages:

  • "The value is negative."

Constraints:

  • sh:MinInclusiveConstraintComponent (Severity: sh:Violation)
    • Value: 0.0

eq452c:NuclearGeneratingUnit​

Severity: sh:Violation

Targets:

  • targetClass: cim:NuclearGeneratingUnit

Nested Properties:

eq452c:GeneratingUnit.minOperatingP-valueRangePair​

Path: cim:GeneratingUnit.minOperatingP
Name: C:452:EQ:GeneratingUnit.minOperatingP:valueRangePair
GeneratingUnit.maxOperatingP shall be greater than or equal to GeneratingUnit.minOperatingP.

Severity: sh:Violation

Messages:

  • "The value is greater than the value of GeneratingUnit.maxOperatingP."

Constraints:

  • sh:LessThanOrEqualsConstraintComponent (Severity: sh:Violation)
    • Path: cim:GeneratingUnit.maxOperatingP

eq452c:OperationalLimitSet​

Severity: sh:Violation

Targets:

  • targetClass: cim:OperationalLimitSet

eq452c:PhaseTapChangerAsymmetrical​

Severity: sh:Violation

Targets:

  • targetClass: cim:PhaseTapChangerAsymmetrical

eq452c:PhaseTapChangerLinear​

Severity: sh:Violation

Targets:

  • targetClass: cim:PhaseTapChangerLinear

eq452c:PhaseTapChangerSymmetrical​

Severity: sh:Violation

Targets:

  • targetClass: cim:PhaseTapChangerSymmetrical

eq452c:PhaseTapChangerTabular​

Severity: sh:Violation

Targets:

  • targetClass: cim:PhaseTapChangerTabular

eq452c:PowerTransformer​

Severity: sh:Violation

Targets:

  • targetClass: cim:PowerTransformer

Nested Properties:

eq452c:PowerTransformer-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:PowerTransformer:containment
For PowerTransformer the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type Substation or DCConverterUnit. For the case of a transformer that connects two substations, the terminal of one of the PowerTransformerEnd-s can be connected to a ConnectivityNode defined in another substation.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not Substation or DCConverterUnit."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Substation cim:DCConverterUnit]

eq452c:PowerTransformerEnd​

Severity: sh:Violation

Targets:

  • targetClass: cim:PowerTransformerEnd

Nested Properties:

eq452c:PowerTransformerEnd.b-valueRange​

Path: cim:PowerTransformerEnd.b
Name: C:452:EQ:PowerTransformerEnd.b:valueRange
PowerTransformerEnd.b shall be negative value or zero. Negative magnetising branch susceptance (PowerTransformerEnd.b) means inductive reactive power losses in no load.

Severity: sh:Violation

Messages:

  • "The value is positive."

Constraints:

  • sh:MaxInclusiveConstraintComponent (Severity: sh:Violation)
    • Value: 0.0

eq452c:PowerTransformerEnd.g-valueRange​

Path: cim:PowerTransformerEnd.g
Name: C:452:EQ:PowerTransformerEnd.g:valueRange
PowerTransformerEnd.g shall be positive value or zero. Positive magnetising branch conductance (PowerTransformerEnd.g) means positive active power losses in no load.

Severity: sh:Violation

Messages:

  • "The value is negative."

Constraints:

  • sh:MinInclusiveConstraintComponent (Severity: sh:Violation)
    • Value: 0.0

eq452c:ProtectedSwitch​

Severity: sh:Violation

Targets:

  • targetClass: cim:Breaker
  • targetClass: cim:DisconnectingCircuitBreaker
  • targetClass: cim:LoadBreakSwitch

Nested Properties:

eq452c:ProtectedSwitch-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:ProtectedSwitch:containment
For ProtectedSwitch (Breaker, DisconnectingCircuitBreaker, LoadBreakSwitch) the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type Bay, VoltageLevel or DCConverterUnit.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not Bay, VoltageLevel or DCConverterUnit."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Bay cim:VoltageLevel cim:DCConverterUnit]

eq452c:RatioTapChanger​

Severity: sh:Violation

Targets:

  • targetClass: cim:RatioTapChanger

eq452c:ReactiveCapabilityCurve​

Severity: sh:Violation

Targets:

  • targetClass: cim:ReactiveCapabilityCurve

eq452c:RegulatingControl​

Severity: sh:Violation

Targets:

  • targetClass: cim:RegulatingControl

Nested Properties:

eq452c:RegulatingControl-RegulatingEquipment​

Path: ^cim:RegulatingCondEq.RegulatingControl
Name: C:452:EQ:RegulatingControl:RegulatingEquipment
A RegulatingControl that is not a TapChangerControl must have at least one regulating equipment associated through the RegulatingCondEq.RegulatingControl. That is, a RegulatingControl cannot exist without some equipment using it for regulating.

Severity: sh:Violation

Messages:

  • "The RegulatingControl is not associated with an Equpment via RegulatingCondEq.RegulatingControl."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1

eq452c:SeriesCompensator​

Severity: sh:Violation

Targets:

  • targetClass: cim:SeriesCompensator

Nested Properties:

eq452c:ConductingEquipment.BaseVoltage-whereRequired​

Path: cim:ConductingEquipment.BaseVoltage
Name: C:452:EQ:ConductingEquipment.BaseVoltage:whereRequired
The ConductingEquipment.BaseVoltage association is required for the following ConductingEquipment: ACLineSegment, EquivalentBranch and SeriesCompensator. For all other Equipment-s, not contained in a VoltageLevel, the association ConductingEquipment.BaseVoltage can be provided (as it is optional), however the association to BaseVoltage coming from the container or transformer ends takes precedence.

Severity: sh:Violation

Messages:

  • "The association ConductingEquipment.BaseVoltage is not provided."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1

eq452c:SeriesCompensator-containment​

Path: cim:Equipment.EquipmentContainer / rdf:type
Name: C:452:EQ:SeriesCompensator:containment
For SeriesCompensator the association Equipment.EquipmentContainer is required and shall point to EquipmentContainer of type VoltageLevel when in substation, DCConverterUnit or Line when outside substation.

Severity: sh:Violation

Messages:

  • "The containment is either missing or it is not VoltageLevel, Line or DCConverterUnit."

Constraints:

  • sh:MinCountConstraintComponent (Severity: sh:Violation)
    • MinCount: 1
  • sh:MaxCountConstraintComponent (Severity: sh:Violation)
    • MaxCount: 1
  • sh:InConstraintComponent (Severity: sh:Violation)
    • Values: [cim:Line cim:VoltageLevel cim:DCConverterUnit]

eq452c:SolarGeneratingUnit​

Severity: sh:Violation

Targets:

  • targetClass: cim:SolarGeneratingUnit

Nested Properties:

eq452c:GeneratingUnit.minOperatingP-valueRangePair​

Path: cim:GeneratingUnit.minOperatingP
Name: C:452:EQ:GeneratingUnit.minOperatingP:valueRangePair
GeneratingUnit.maxOperatingP shall be greater than or equal to GeneratingUnit.minOperatingP.

Severity: sh:Violation

Messages:

  • "The value is greater than the value of GeneratingUnit.maxOperatingP."

Constraints:

  • sh:LessThanOrEqualsConstraintComponent (Severity: sh:Violation)
    • Path: cim:GeneratingUnit.maxOperatingP

eq452c:StaticVarCompensator​

Severity: sh:Violation

Targets:

  • targetClass: cim:StaticVarCompensator

eq452c:Switch​

Severity: sh:Violation

Targets:

  • targetClass: cim:Switch

eq452c:SynchronousMachine​

Severity: sh:Violation

Targets:

  • targetClass: cim:SynchronousMachine

Nested Properties:

eq452c:SynchronousMachine.minQ-valueRangePair​

Path: cim:SynchronousMachine.minQ
Name: C:452:EQ:SynchronousMachine.maxQ:valueRangePair
SynchronousMachine.maxQ shall be greater than or equal to SynchronousMachine.minQ.

Severity: sh:Violation

Messages:

  • "The value is greater than the value of SynchronousMachine.maxQ."

Constraints:

  • sh:LessThanOrEqualsConstraintComponent (Severity: sh:Violation)
    • Path: cim:SynchronousMachine.maxQ

eq452c:TapChangerControl​

Severity: sh:Violation

Targets:

  • targetClass: cim:TapChangerControl

eq452c:ThermalGeneratingUnit​

Severity: sh:Violation

Targets:

  • targetClass: cim:ThermalGeneratingUnit

Nested Properties:

eq452c:GeneratingUnit.minOperatingP-valueRangePair​

Path: cim:GeneratingUnit.minOperatingP
Name: C:452:EQ:GeneratingUnit.minOperatingP:valueRangePair
GeneratingUnit.maxOperatingP shall be greater than or equal to GeneratingUnit.minOperatingP.

Severity: sh:Violation

Messages:

  • "The value is greater than the value of GeneratingUnit.maxOperatingP."

Constraints:

  • sh:LessThanOrEqualsConstraintComponent (Severity: sh:Violation)
    • Path: cim:GeneratingUnit.maxOperatingP

eq452c:VsCapabilityCurve​

Severity: sh:Violation

Targets:

  • targetClass: cim:VsCapabilityCurve

eq452c:WindGeneratingUnit​

Severity: sh:Violation

Targets:

  • targetClass: cim:WindGeneratingUnit

Nested Properties:

eq452c:GeneratingUnit.minOperatingP-valueRangePair​

Path: cim:GeneratingUnit.minOperatingP
Name: C:452:EQ:GeneratingUnit.minOperatingP:valueRangePair
GeneratingUnit.maxOperatingP shall be greater than or equal to GeneratingUnit.minOperatingP.

Severity: sh:Violation

Messages:

  • "The value is greater than the value of GeneratingUnit.maxOperatingP."

Constraints:

  • sh:LessThanOrEqualsConstraintComponent (Severity: sh:Violation)
    • Path: cim:GeneratingUnit.maxOperatingP