61970-301_ShortCircuit-AP-Con-Complex-SHACL
sc:MutualCoupling
Severity: sh:Violation
Targets:
- targetClass: cim:MutualCoupling
Nested Properties:
sc:MutualCoupling.distance11-lengthValueRange
Path: cim:MutualCoupling.distance11
Length datatype defines that: It shall be a positive value or zero.
Severity: sh:Violation
Messages:
- "The value is negative."
Constraints:
- sh:MinInclusiveConstraintComponent (Severity: sh:Violation)
- Value:
0.0
- Value:
sc:MutualCoupling.distance12-lengthValueRange
Path: cim:MutualCoupling.distance12
Length datatype defines that: It shall be a positive value or zero.
Severity: sh:Violation
Messages:
- "The value is negative."
Constraints:
- sh:MinInclusiveConstraintComponent (Severity: sh:Violation)
- Value:
0.0
- Value:
sc:MutualCoupling.distance21-lengthValueRange
Path: cim:MutualCoupling.distance21
Length datatype defines that: It shall be a positive value or zero.
Severity: sh:Violation
Messages:
- "The value is negative."
Constraints:
- sh:MinInclusiveConstraintComponent (Severity: sh:Violation)
- Value:
0.0
- Value:
sc:MutualCoupling.distance22-lengthValueRange
Path: cim:MutualCoupling.distance22
Length datatype defines that: It shall be a positive value or zero.
Severity: sh:Violation
Messages:
- "The value is negative."
Constraints:
- sh:MinInclusiveConstraintComponent (Severity: sh:Violation)
- Value:
0.0
- Value:
sc:PetersenCoil
Severity: sh:Violation
Targets:
- targetClass: cim:PetersenCoil
Nested Properties:
sc:PetersenCoil.offsetCurrent-valueRangeTypical
Path: cim:PetersenCoil.offsetCurrent
This is normally a fixed amount for which the controller is configured and could be positive or negative. Typically 0 to 60 A depending on voltage and resonance conditions.
Severity: sh:Warning
Messages:
- "The value is outside the range: 0-60 A."
Constraints:
- sh:MinInclusiveConstraintComponent (Severity: sh:Warning)
- Value:
0.0
- Value:
- sh:MaxInclusiveConstraintComponent (Severity: sh:Warning)
- Value:
60
- Value:
sc:PetersenCoil.positionCurrent-valueRangeTypical
Path: cim:PetersenCoil.positionCurrent
Typically in the range of 20 mA to 200 mA.
Severity: sh:Warning
Messages:
- "The value is outside the range: 20-200 mA."
Constraints:
- sh:MinInclusiveConstraintComponent (Severity: sh:Warning)
- Value:
0.02
- Value:
- sh:MaxInclusiveConstraintComponent (Severity: sh:Warning)
- Value:
0.2
- Value:
sc:PowerTransformerEnd
Severity: sh:Violation
Targets:
- targetClass: cim:PowerTransformerEnd
Nested Properties:
sc:PowerTransformerEnd.phaseAngleClock-valueRange
Path: cim:PowerTransformerEnd.phaseAngleClock
The valid values are 0 to 11.
Severity: sh:Violation
Messages:
- "The value is outside the valid range: 0-11."
Constraints:
- sh:MinInclusiveConstraintComponent (Severity: sh:Violation)
- Value:
0.0
- Value:
- sh:MaxInclusiveConstraintComponent (Severity: sh:Violation)
- Value:
11.0
- Value:
sc:SeriesCompensator
Severity: sh:Violation
Targets:
- targetClass: cim:SeriesCompensator
Nested Properties:
sc:SeriesCompensator.varistorRatedCurrent-valueRange
Path: cim:SeriesCompensator.varistorRatedCurrent
The attribute shall be a positive value.
Severity: sh:Violation
Messages:
- "The value is negative or zero."
Constraints:
- sh:MinExclusiveConstraintComponent (Severity: sh:Violation)
- Value:
0.0
- Value: