WindPlantFreqPcontrolIEC

Frequency and active power controller model. Reference: IEC 61400-27-1:2015, Annex D.

Inheritance

Attributes

LabelTypeMultiplicityComment
WindDynamicsLookupTableWindDynamicsLookupTable1..nThe wind dynamics lookup table associated with this frequency and active power wind plant model.
WindPlantIECWindPlantIEC1Wind plant model with which this wind plant frequency and active power control is associated.
dprefmaxFloat1..1Maximum ramp rate of pWTref request from the plant controller to the wind turbines (dprefmax) (> WindPlantFreqPcontrolIEC.dprefmin). It is a case-dependent parameter.
dprefminFloat1..1Minimum (negative) ramp rate of pWTref request from the plant controller to the wind turbines (dprefmin) (< WindPlantFreqPcontrolIEC.dprefmax). It is a project-dependent parameter.
dpwprefmaxFloat1..1Maximum positive ramp rate for wind plant power reference (dpWPrefmax) (> WindPlantFreqPcontrolIEC.dpwprefmin). It is a project-dependent parameter.
dpwprefminFloat1..1Maximum negative ramp rate for wind plant power reference (dpWPrefmin) (< WindPlantFreqPcontrolIEC.dpwprefmax). It is a project-dependent parameter.
kiwppFloat1..1Plant P controller integral gain (KIWPp). It is a project-dependent parameter.
kiwppmaxFloat1..1Maximum PI integrator term (KIWPpmax) (> WindPlantFreqPcontrolIEC.kiwppmin). It is a project-dependent parameter.
kiwppminFloat1..1Minimum PI integrator term (KIWPpmin) (< WindPlantFreqPcontrolIEC.kiwppmax). It is a project-dependent parameter.
kpwppFloat1..1Plant P controller proportional gain (KPWPp). It is a project-dependent parameter.
kwpprefFloat1..1Power reference gain (KWPpref). It is a project-dependent parameter.
prefmaxFloat1..1Maximum pWTref request from the plant controller to the wind turbines (prefmax) (> WindPlantFreqPcontrolIEC.prefmin). It is a project-dependent parameter.
prefminFloat1..1Minimum pWTref request from the plant controller to the wind turbines (prefmin) (< WindPlantFreqPcontrolIEC.prefmax). It is a project-dependent parameter.
tpftFloat1..1Lead time constant in reference value transfer function (Tpft) (>= 0). It is a project-dependent parameter.
tpfvFloat1..1Lag time constant in reference value transfer function (Tpfv) (>= 0). It is a project-dependent parameter.
twpffiltpFloat1..1Filter time constant for frequency measurement (TWPffiltp) (>= 0). It is a project-dependent parameter.
twppfiltpFloat1..1Filter time constant for active power measurement (TWPpfiltp) (>= 0). It is a project-dependent parameter.