WindLookupTableFunctionKind (Enumeration)

Function of the lookup table.

Values

LabelComment
prrPower versus speed change (negative slip) lookup table (prr(deltaomega)). It is used for the rotor resistance control model, IEC 61400-27-1:2015, 5.6.5.3.
omegapPower vs. speed lookup table (omega(p)). It is used for the P control model type 3, IEC 61400-27-1:2015, 5.6.5.4.
ipmaxLookup table for voltage dependency of active current limits (ipmax(uWT)). It is used for the current limitation model, IEC 61400-27-1:2015, 5.6.5.8.
iqmaxLookup table for voltage dependency of reactive current limits (iqmax(uWT)). It is used for the current limitation model, IEC 61400-27-1:2015, 5.6.5.8.
pwpPower vs. frequency lookup table (pWPbias(f)). It is used for the wind power plant frequency and active power control model, IEC 61400-27-1:2015, Annex D.
tcwduCrowbar duration versus voltage variation look-up table (TCW(du)). It is a case-dependent parameter. It is used for the type 3B generator set model, IEC 61400-27-1:2015, 5.6.3.3.
tduwtLookup table to determine the duration of the power reduction after a voltage dip, depending on the size of the voltage dip (Td(uWT)). It is a type-dependent parameter. It is used for the pitch control power model, IEC 61400-27-1:2015, 5.6.5.1.
qmaxpLookup table for active power dependency of reactive power maximum limit (qmaxp(p)). It is used for the QP and QU limitation model, IEC 61400-27-1:2015, 5.6.5.10.
qminpLookup table for active power dependency of reactive power minimum limit (qminp(p)). It is used for the QP and QU limitation model, IEC 61400-27-1:2015, 5.6.5.10.
qmaxuLookup table for voltage dependency of reactive power maximum limit (qmaxu(p)). It is used for the QP and QU limitation model, IEC 61400-27-1:2015, 5.6.5.10.
qminuLookup table for voltage dependency of reactive power minimum limit (qminu(p)). It is used for the QP and QU limitation model, IEC 61400-27-1:2015, 5.6.5.10.
tuoverDisconnection time versus over-voltage lookup table (Tuover(uWT)). It is used for the grid protection model, IEC 61400-27-1:2015, 5.6.6.
tuunderDisconnection time versus under-voltage lookup table (Tuunder(uWT)). It is used for the grid protection model, IEC 61400-27-1:2015, 5.6.6.
tfoverDisconnection time versus over-frequency lookup table (Tfover(fWT)). It is used for the grid protection model, IEC 61400-27-1:2015, 5.6.6.
tfunderDisconnection time versus under-frequency lookup table (Tfunder(fWT)). It is used for the grid protection model, IEC 61400-27-1:2015, 5.6.6.
qwpLook up table for the UQ static mode (qWP(uerr)). It is used for the voltage and reactive power control model, IEC 61400-27-1:2015, Annex D.