Current limitation model. The current limitation model combines the physical limits and the control limits. Reference: IEC 61400-27-1:2015, 5.6.5.8.

Inheritance

Attributes

LabelTypeMultiplicityComment
WindDynamicsLookupTableWindDynamicsLookupTable1..nThe wind dynamics lookup table associated with this current control limitation model.
WindTurbineType3or4IECWindTurbineType3or4IEC1Wind turbine type 3 or type 4 model with which this wind control current limitation model is associated.
imaxFloat1..1Maximum continuous current at the wind turbine terminals (imax). It is a type-dependent parameter.
imaxdipFloat1..1Maximum current during voltage dip at the wind turbine terminals (imaxdip). It is a project-dependent parameter.
kpquFloat1..1Partial derivative of reactive current limit (Kpqu) versus voltage. It is a type-dependent parameter.
mdfslimBoolean1..1Limitation of type 3 stator current (MDFSLim). MDFSLim = 1 for wind turbines type 4. It is a type-dependent parameter. false= total current limitation (0 in the IEC model) true=stator current limitation (1 in the IEC model).
mqpriBoolean1..1Prioritisation of Q control during UVRT (Mqpri). It is a project-dependent parameter. true = reactive power priority (1 in the IEC model) false = active power priority (0 in the IEC model).
tufiltclFloat1..1Voltage measurement filter time constant (Tufiltcl) (>= 0). It is a type-dependent parameter.
upqumaxFloat1..1Wind turbine voltage in the operation point where zero reactive current can be delivered (upqumax). It is a type-dependent parameter.