PssSH

SiemensTM “H infinity” power system stabilizer with generator electrical power input. [Footnote: Siemens 'H infinity' power system stabilizers are an example of suitable products available commercially. This information is given for the convenience of users of this document and does not constitute an endorsement by IEC of these products.]

Inheritance

Attributes

LabelTypeMultiplicityComment
kFloat1..1Main gain (K). Typical value = 1.
k0Float1..1Gain 0 (K0). Typical value = 0,012.
k1Float1..1Gain 1 (K1). Typical value = 0,488.
k2Float1..1Gain 2 (K2). Typical value = 0,064.
k3Float1..1Gain 3 (K3). Typical value = 0,224.
k4Float1..1Gain 4 (K4). Typical value = 0,1.
t1Float1..1Time constant 1 (T1) (> 0). Typical value = 0,076.
t2Float1..1Time constant 2 (T2) (> 0). Typical value = 0,086.
t3Float1..1Time constant 3 (T3) (> 0). Typical value = 1,068.
t4Float1..1Time constant 4 (T4) (> 0). Typical value = 1,913.
tdFloat1..1Input time constant (Td) (>= 0). Typical value = 10.
vsmaxFloat1..1Output maximum limit (Vsmax) (> PssSH.vsmin). Typical value = 0,1.
vsminFloat1..1Output minimum limit (Vsmin) (< PssSH.vsmax). Typical value = -0,1.