Skip to main content

PFVArType1IEEEVArController

IEEE VAR controller type 1 which operates by moving the voltage reference directly. Reference: IEEE 421.5-2005, 11.3.

Inheritance

Attributes

LabelTypeMultiplicityComment
tvarcFloat1..1Var controller time delay (TVARC) (>= 0). Typical value = 5.
vvarFloat1..1Synchronous machine power factor (VVAR).
vvarcbwFloat1..1Var controller deadband (VVARC_BW). Typical value = 0,02.
vvarrefFloat1..1Var controller reference (VVARREF).
vvtmaxFloat1..1Maximum machine terminal voltage needed for pf/VAr controller to be enabled (VVTMAX) (> PVFArType1IEEEVArController.vvtmin).
vvtminFloat1..1Minimum machine terminal voltage needed to enable pf/var controller (VVTMIN) (< PVFArType1IEEEVArController.vvtmax).