Skip to main content

OverexcLim2

Different from LimIEEEOEL, LimOEL2 has a fixed pickup threshold and reduces the excitation set-point by means of a non-windup integral regulator. Irated is the rated machine excitation current (calculated from nameplate conditions: Vnom, Pnom, CosPhinom).

Inheritance

Attributes

LabelTypeMultiplicityComment
ifdlimFloat1..1Limit value of rated field current (IFDLIM). Typical value = 1,05.
koiFloat1..1Gain Over excitation limiter (KOI). Typical value = 0,1.
voimaxFloat1..1Maximum error signal (VOIMAX) (> OverexcLim2.voimin). Typical value = 0.
voiminFloat1..1Minimum error signal (VOIMIN) (< OverexcLim2.voimax). Typical value = -9999.