Skip to main content

LoadGenericNonLinear

Generic non-linear dynamic (GNLD) load. This model can be used in mid-term and long-term voltage stability simulations (i.e., to study voltage collapse), as it can replace a more detailed representation of aggregate load, including induction motors, thermostatically controlled and static loads.

Inheritance​

Attributes​

LabelTypeMultiplicityComment
bsFloat1..1Steady state voltage index for reactive power (BS).
btFloat1..1Transient voltage index for reactive power (BT).
genericNonLinearLoadModelTypeGenericNonLinearLoadModelKind1..1Type of generic non-linear load model.
lsFloat1..1Steady state voltage index for active power (LS).
ltFloat1..1Transient voltage index for active power (LT).
tpFloat1..1Time constant of lag function of active power (TP) (> 0).
tqFloat1..1Time constant of lag function of reactive power (TQ) (> 0).