GovSteamFV3

Simplified GovSteamIEEE1 steam turbine governor with Prmax limit and fast valving.

Inheritance

Attributes

LabelTypeMultiplicityComment
gv1Float1..1Nonlinear gain valve position point 1 (GV1). Typical value = 0.
gv2Float1..1Nonlinear gain valve position point 2 (GV2). Typical value = 0,4.
gv3Float1..1Nonlinear gain valve position point 3 (GV3). Typical value = 0,5.
gv4Float1..1Nonlinear gain valve position point 4 (GV4). Typical value = 0,6.
gv5Float1..1Nonlinear gain valve position point 5 (GV5). Typical value = 1.
gv6Float1..1Nonlinear gain valve position point 6 (GV6). Typical value = 0.
kFloat1..1Governor gain, (reciprocal of droop) (K). Typical value = 20.
k1Float1..1Fraction of turbine power developed after first boiler pass (K1). Typical value = 0,2.
k2Float1..1Fraction of turbine power developed after second boiler pass (K2). Typical value = 0,2.
k3Float1..1Fraction of hp turbine power developed after crossover or third boiler pass (K3). Typical value = 0,6.
mwbaseFloat1..1Base for power values (MWbase) (> 0). Unit = MW.
pgv1Float1..1Nonlinear gain power value point 1 (Pgv1). Typical value = 0.
pgv2Float1..1Nonlinear gain power value point 2 (Pgv2). Typical value = 0,75.
pgv3Float1..1Nonlinear gain power value point 3 (Pgv3). Typical value = 0,91.
pgv4Float1..1Nonlinear gain power value point 4 (Pgv4). Typical value = 0,98.
pgv5Float1..1Nonlinear gain power value point 5 (Pgv5). Typical value = 1.
pgv6Float1..1Nonlinear gain power value point 6 (Pgv6). Typical value = 0.
pmaxFloat1..1Maximum valve opening, PU of MWbase (Pmax) (> GovSteamFV3.pmin). Typical value = 1.
pminFloat1..1Minimum valve opening, PU of MWbase (Pmin) (< GovSteamFV3.pmax). Typical value = 0.
prmaxFloat1..1Max. pressure in reheater (Prmax). Typical value = 1.
t1Float1..1Governor lead time constant (T1) (>= 0). Typical value = 0.
t2Float1..1Governor lag time constant (T2) (>= 0). Typical value = 0.
t3Float1..1Valve positioner time constant (T3) (> 0). Typical value = 0.
t4Float1..1Inlet piping/steam bowl time constant (T4) (>= 0). Typical value = 0,2.
t5Float1..1Time constant of second boiler pass (i.e. reheater) (T5) (> 0 if fast valving is used, otherwise >= 0). Typical value = 0,5.
t6Float1..1Time constant of crossover or third boiler pass (T6) (>= 0). Typical value = 10.
taFloat1..1Time to close intercept valve (IV) (Ta) (>= 0). Typical value = 0,97.
tbFloat1..1Time until IV starts to reopen (Tb) (>= 0). Typical value = 0,98.
tcFloat1..1Time until IV is fully open (Tc) (>= 0). Typical value = 0,99.
ucFloat1..1Maximum valve closing velocity (Uc). Unit = PU / s. Typical value = -1.
uoFloat1..1Maximum valve opening velocity (Uo). Unit = PU / s. Typical value = 0,1.