Skip to main content

GovSteamFV2

Steam turbine governor with reheat time constants and modelling of the effects of fast valve closing to reduce mechanical power.

Inheritance​

Attributes​

LabelTypeMultiplicityComment
dtFloat1..1(Dt).
kFloat1..1Fraction of the turbine power developed by turbine sections not involved in fast valving (K).
mwbaseFloat1..1Alternate base used instead of machine base in equipment model if necessary (MWbase) (> 0). Unit = MW.
rFloat1..1(R).
t1Float1..1Governor time constant (T1) (>= 0).
t3Float1..1Reheater time constant (T3) (>= 0).
taFloat1..1Time after initial time for valve to close (Ta) (>= 0).
tbFloat1..1Time after initial time for valve to begin opening (Tb) (>= 0).
tcFloat1..1Time after initial time for valve to become fully open (Tc) (>= 0).
ttFloat1..1Time constant with which power falls off after intercept valve closure (Tt) (>= 0).
vmaxFloat1..1(Vmax) (> GovSteamFV2.vmin).
vminFloat1..1(Vmin) (< GovSteamFV2.vmax).