GovSteam1

Steam turbine governor, based on the GovSteamIEEE1 (with optional deadband and nonlinear valve gain added).

Inheritance

Attributes

LabelTypeMultiplicityComment
db1Float1..1Intentional deadband width (db1). Unit = Hz. Typical value = 0.
db2Float1..1Unintentional deadband (db2). Unit = MW. Typical value = 0.
epsFloat1..1Intentional db hysteresis (eps). Unit = Hz. Typical value = 0.
gv1Float1..1Nonlinear gain valve position point 1 (GV1). Typical value = 0.
gv2Float1..1Nonlinear gain valve position point 2 (GV2). Typical value = 0,4.
gv3Float1..1Nonlinear gain valve position point 3 (GV3). Typical value = 0,5.
gv4Float1..1Nonlinear gain valve position point 4 (GV4). Typical value = 0,6.
gv5Float1..1Nonlinear gain valve position point 5 (GV5). Typical value = 1.
gv6Float1..1Nonlinear gain valve position point 6 (GV6). Typical value = 0.
kFloat1..1Governor gain (reciprocal of droop) (K) (> 0). Typical value = 25.
k1Float1..1Fraction of HP shaft power after first boiler pass (K1). Typical value = 0,2.
k2Float1..1Fraction of LP shaft power after first boiler pass (K2). Typical value = 0.
k3Float1..1Fraction of HP shaft power after second boiler pass (K3). Typical value = 0,3.
k4Float1..1Fraction of LP shaft power after second boiler pass (K4). Typical value = 0.
k5Float1..1Fraction of HP shaft power after third boiler pass (K5). Typical value = 0,5.
k6Float1..1Fraction of LP shaft power after third boiler pass (K6). Typical value = 0.
k7Float1..1Fraction of HP shaft power after fourth boiler pass (K7). Typical value = 0.
k8Float1..1Fraction of LP shaft power after fourth boiler pass (K8). Typical value = 0.
mwbaseFloat1..1Base for power values (MWbase) (> 0). Unit = MW.
pgv1Float1..1Nonlinear gain power value point 1 (Pgv1). Typical value = 0.
pgv2Float1..1Nonlinear gain power value point 2 (Pgv2). Typical value = 0,75.
pgv3Float1..1Nonlinear gain power value point 3 (Pgv3). Typical value = 0,91.
pgv4Float1..1Nonlinear gain power value point 4 (Pgv4). Typical value = 0,98.
pgv5Float1..1Nonlinear gain power value point 5 (Pgv5). Typical value = 1.
pgv6Float1..1Nonlinear gain power value point 6 (Pgv6). Typical value = 0.
pmaxFloat1..1Maximum valve opening (Pmax) (> GovSteam1.pmin). Typical value = 1.
pminFloat1..1Minimum valve opening (Pmin) (>= 0 and < GovSteam1.pmax). Typical value = 0.
sdb1Boolean1..1Intentional deadband indicator. true = intentional deadband is applied false = intentional deadband is not applied. Typical value = true.
sdb2Boolean1..1Unintentional deadband location. true = intentional deadband is applied before point 'A' false = intentional deadband is applied after point 'A'. Typical value = true.
t1Float1..1Governor lag time constant (T1) (>= 0). Typical value = 0.
t2Float1..1Governor lead time constant (T2) (>= 0). Typical value = 0.
t3Float1..1Valve positioner time constant (T3) (> 0). Typical value = 0,1.
t4Float1..1Inlet piping/steam bowl time constant (T4) (>= 0). Typical value = 0,3.
t5Float1..1Time constant of second boiler pass (T5) (>= 0). Typical value = 5.
t6Float1..1Time constant of third boiler pass (T6) (>= 0). Typical value = 0,5.
t7Float1..1Time constant of fourth boiler pass (T7) (>= 0). Typical value = 0.
ucFloat1..1Maximum valve closing velocity (Uc) (< 0). Unit = PU / s. Typical value = -10.
uoFloat1..1Maximum valve opening velocity (Uo) (> 0). Unit = PU / s. Typical value = 1.
valveBoolean1..1Nonlinear valve characteristic. true = nonlinear valve characteristic is used false = nonlinear valve characteristic is not used. Typical value = true.