Skip to main content

GovSteam0

A simplified steam turbine governor.

Inheritance

Attributes

LabelTypeMultiplicityComment
dtFloat1..1Turbine damping coefficient (Dt). Unit = delta P / delta speed. Typical value = 0.
mwbaseFloat1..1Base for power values (MWbase) (> 0). Unit = MW.
rFloat1..1Permanent droop (R). Typical value = 0,05.
t1Float1..1Steam bowl time constant (T1) (> 0). Typical value = 0,5.
t2Float1..1Numerator time constant of T2/T3 block (T2) (>= 0). Typical value = 3.
t3Float1..1Reheater time constant (T3) (> 0). Typical value = 10.
vmaxFloat1..1Maximum valve position, PU of mwcap (Vmax) (> GovSteam0.vmin). Typical value = 1.
vminFloat1..1Minimum valve position, PU of mwcap (Vmin) (< GovSteam0.vmax). Typical value = 0.