GovHydroWPID

WoodwardTM PID hydro governor. [Footnote: Woodward PID hydro governors are an example of suitable products available commercially. This information is given for the convenience of users of this document and does not constitute an endorsement by IEC of these products.]

Inheritance

Attributes

LabelTypeMultiplicityComment
dFloat1..1Turbine damping factor (D). Unit = delta P / delta speed.
gatmaxFloat1..1Gate opening limit maximum (Gatmax) (> GovHydroWPID.gatmin).
gatminFloat1..1Gate opening limit minimum (Gatmin) (< GovHydroWPID.gatmax).
gv1Float1..1Gate position 1 (Gv1).
gv2Float1..1Gate position 2 (Gv2).
gv3Float1..1Gate position 3 (Gv3) (= 1,0).
kdFloat1..1Derivative gain (Kd). Typical value = 1,11.
kiFloat1..1Reset gain (Ki). Typical value = 0,36.
kpFloat1..1Proportional gain (Kp). Typical value = 0,1.
mwbaseFloat1..1Base for power values (MWbase) (> 0). Unit = MW.
pgv1Float1..1Output at Gv1 PU of MWbase (Pgv1).
pgv2Float1..1Output at Gv2 PU of MWbase (Pgv2).
pgv3Float1..1Output at Gv3 PU of MWbase (Pgv3).
pmaxFloat1..1Maximum power output (Pmax) (> GovHydroWPID.pmin).
pminFloat1..1Minimum power output (Pmin) (< GovHydroWPID.pmax).
regFloat1..1Permanent drop (Reg).
taFloat1..1Controller time constant (Ta) (>= 0). Typical value = 0.
tbFloat1..1Gate servo time constant (Tb) (>= 0). Typical value = 0.
tregFloat1..1Speed detector time constant (Treg) (>= 0).
twFloat1..1Water inertia time constant (Tw) (>= 0). Typical value = 0.
velmaxFloat1..1Maximum gate opening velocity (Velmax) (> GovHydroWPID.velmin). Unit = PU / s. Typical value = 0.
velminFloat1..1Maximum gate closing velocity (Velmin) (< GovHydroWPID.velmax). Unit = PU / s. Typical value = 0.