GovHydroR

Fourth order lead-lag governor and hydro turbine.

Inheritance

Attributes

LabelTypeMultiplicityComment
atFloat1..1Turbine gain (At). Typical value = 1,2.
db1Float1..1Intentional dead-band width (db1). Unit = Hz. Typical value = 0.
db2Float1..1Unintentional dead-band (db2). Unit = MW. Typical value = 0.
dturbFloat1..1Turbine damping factor (Dturb). Typical value = 0,2.
epsFloat1..1Intentional db hysteresis (eps). Unit = Hz. Typical value = 0.
gmaxFloat1..1Maximum governor output (Gmax) (> GovHydroR.gmin). Typical value = 1,05.
gminFloat1..1Minimum governor output (Gmin) (< GovHydroR.gmax). Typical value = -0,05.
gv1Float1..1Nonlinear gain point 1, PU gv (Gv1). Typical value = 0.
gv2Float1..1Nonlinear gain point 2, PU gv (Gv2). Typical value = 0.
gv3Float1..1Nonlinear gain point 3, PU gv (Gv3). Typical value = 0.
gv4Float1..1Nonlinear gain point 4, PU gv (Gv4). Typical value = 0.
gv5Float1..1Nonlinear gain point 5, PU gv (Gv5). Typical value = 0.
gv6Float1..1Nonlinear gain point 6, PU gv (Gv6). Typical value = 0.
h0Float1..1Turbine nominal head (H0). Typical value = 1.
inputSignalBoolean1..1Input signal switch (Flag). true = Pe input is used false = feedback is received from CV. Flag is normally dependent on Tt. If Tt is zero, Flag is set to false. If Tt is not zero, Flag is set to true. Typical value = true.
kgFloat1..1Gate servo gain (Kg). Typical value = 2.
kiFloat1..1Integral gain (Ki). Typical value = 0,5.
mwbaseFloat1..1Base for power values (MWbase) (> 0). Unit = MW.
pgv1Float1..1Nonlinear gain point 1, PU power (Pgv1). Typical value = 0.
pgv2Float1..1Nonlinear gain point 2, PU power (Pgv2). Typical value = 0.
pgv3Float1..1Nonlinear gain point 3, PU power (Pgv3). Typical value = 0.
pgv4Float1..1Nonlinear gain point 4, PU power (Pgv4). Typical value = 0.
pgv5Float1..1Nonlinear gain point 5, PU power (Pgv5). Typical value = 0.
pgv6Float1..1Nonlinear gain point 6, PU power (Pgv6). Typical value = 0.
pmaxFloat1..1Maximum gate opening, PU of MWbase (Pmax) (> GovHydroR.pmin). Typical value = 1.
pminFloat1..1Minimum gate opening, PU of MWbase (Pmin) (< GovHydroR.pmax). Typical value = 0.
qnlFloat1..1No-load turbine flow at nominal head (Qnl). Typical value = 0,08.
rFloat1..1Steady-state droop (R). Typical value = 0,05.
t1Float1..1Lead time constant 1 (T1) (>= 0). Typical value = 1,5.
t2Float1..1Lag time constant 1 (T2) (>= 0). Typical value = 0,1.
t3Float1..1Lead time constant 2 (T3) (>= 0). Typical value = 1,5.
t4Float1..1Lag time constant 2 (T4) (>= 0). Typical value = 0,1.
t5Float1..1Lead time constant 3 (T5) (>= 0). Typical value = 0.
t6Float1..1Lag time constant 3 (T6) (>= 0). Typical value = 0,05.
t7Float1..1Lead time constant 4 (T7) (>= 0). Typical value = 0.
t8Float1..1Lag time constant 4 (T8) (>= 0). Typical value = 0,05.
tdFloat1..1Input filter time constant (Td) (>= 0). Typical value = 0,05.
tpFloat1..1Gate servo time constant (Tp) (>= 0). Typical value = 0,05.
ttFloat1..1Power feedback time constant (Tt) (>= 0). Typical value = 0.
twFloat1..1Water inertia time constant (Tw) (> 0). Typical value = 1.
velclFloat1..1Maximum gate closing velocity (Velcl). Unit = PU / s. Typical value = -0,2.
velopFloat1..1Maximum gate opening velocity (Velop). Unit = PU / s. Typical value = 0,2.