GovHydroPID

PID governor and turbine.

Inheritance

Attributes

LabelTypeMultiplicityComment
aturbFloat1..1Turbine numerator multiplier (Aturb) (see parameter detail 3). Typical value -1.
bturbFloat1..1Turbine denominator multiplier (Bturb) (see parameter detail 3). Typical value = 0,5.
db1Float1..1Intentional dead-band width (db1). Unit = Hz. Typical value = 0.
db2Float1..1Unintentional dead-band (db2). Unit = MW. Typical value = 0.
epsFloat1..1Intentional db hysteresis (eps). Unit = Hz. Typical value = 0.
gv1Float1..1Nonlinear gain point 1, PU gv (Gv1). Typical value = 0.
gv2Float1..1Nonlinear gain point 2, PU gv (Gv2). Typical value = 0.
gv3Float1..1Nonlinear gain point 3, PU gv (Gv3). Typical value = 0.
gv4Float1..1Nonlinear gain point 4, PU gv (Gv4). Typical value = 0.
gv5Float1..1Nonlinear gain point 5, PU gv (Gv5). Typical value = 0.
gv6Float1..1Nonlinear gain point 6, PU gv (Gv6). Typical value = 0.
inputSignalBoolean1..1Input signal switch (Flag). true = Pe input is used false = feedback is received from CV. Flag is normally dependent on Tt. If Tt is zero, Flag is set to false. If Tt is not zero, Flag is set to true. Typical value = true.
kdFloat1..1Derivative gain (Kd). Typical value = 1,11.
kgFloat1..1Gate servo gain (Kg). Typical value = 2,5.
kiFloat1..1Integral gain (Ki). Typical value = 0,36.
kpFloat1..1Proportional gain (Kp). Typical value = 0,1.
mwbaseFloat1..1Base for power values (MWbase) (> 0). Unit = MW.
pgv1Float1..1Nonlinear gain point 1, PU power (Pgv1). Typical value = 0.
pgv2Float1..1Nonlinear gain point 2, PU power (Pgv2). Typical value = 0.
pgv3Float1..1Nonlinear gain point 3, PU power (Pgv3). Typical value = 0.
pgv4Float1..1Nonlinear gain point 4, PU power (Pgv4). Typical value = 0.
pgv5Float1..1Nonlinear gain point 5, PU power (Pgv5). Typical value = 0.
pgv6Float1..1Nonlinear gain point 6, PU power (Pgv6). Typical value = 0.
pmaxFloat1..1Maximum gate opening, PU of MWbase (Pmax) (> GovHydroPID.pmin). Typical value = 1.
pminFloat1..1Minimum gate opening, PU of MWbase (Pmin) (< GovHydroPID.pmax). Typical value = 0.
rFloat1..1Steady state droop (R). Typical value = 0,05.
tdFloat1..1Input filter time constant (Td) (>= 0). If = 0, block is bypassed. Typical value = 0.
tfFloat1..1Washout time constant (Tf) (>= 0). Typical value = 0,1.
tpFloat1..1Gate servo time constant (Tp) (>= 0). If = 0, block is bypassed. Typical value = 0,35.
ttFloat1..1Power feedback time constant (Tt) (>= 0). If = 0, block is bypassed. Typical value = 0,02.
tturbFloat1..1Turbine time constant (Tturb) (>= 0). See Parameter detail 3. Typical value = 0,8.
velclFloat1..1Maximum gate closing velocity (Velcl). Unit = PU / s. Typical value = -0,14.
velopFloat1..1Maximum gate opening velocity (Velop). Unit = PU / s. Typical value = 0,09.