Skip to main content

GovHydroIEEE2

IEEE hydro turbine governor model represents plants with straightforward penstock configurations and hydraulic-dashpot governors. Reference: IEEE Transactions on Power Apparatus and Systems, November/December 1973, Volume PAS-92, Number 6, Dynamic Models for Steam and Hydro Turbines in Power System Studies, page 1904.

Inheritance

Attributes

LabelTypeMultiplicityComment
aturbFloat1..1Turbine numerator multiplier (Aturb). Typical value = -1.
bturbFloat1..1Turbine denominator multiplier (Bturb) (> 0). Typical value = 0,5.
gv1Float1..1Nonlinear gain point 1, PU gv (Gv1). Typical value = 0.
gv2Float1..1Nonlinear gain point 2, PU gv (Gv2). Typical value = 0.
gv3Float1..1Nonlinear gain point 3, PU gv (Gv3). Typical value = 0.
gv4Float1..1Nonlinear gain point 4, PU gv (Gv4). Typical value = 0.
gv5Float1..1Nonlinear gain point 5, PU gv (Gv5). Typical value = 0.
gv6Float1..1Nonlinear gain point 6, PU gv (Gv6). Typical value = 0.
kturbFloat1..1Turbine gain (Kturb). Typical value = 1.
mwbaseFloat1..1Base for power values (MWbase) (> 0). Unit = MW.
pgv1Float1..1Nonlinear gain point 1, PU power (Pgv1). Typical value = 0.
pgv2Float1..1Nonlinear gain point 2, PU power (Pgv2). Typical value = 0.
pgv3Float1..1Nonlinear gain point 3, PU power (Pgv3). Typical value = 0.
pgv4Float1..1Nonlinear gain point 4, PU power (Pgv4). Typical value = 0.
pgv5Float1..1Nonlinear gain point 5, PU power (Pgv5). Typical value = 0.
pgv6Float1..1Nonlinear gain point 6, PU power (Pgv6). Typical value = 0.
pmaxFloat1..1Maximum gate opening (Pmax) (> GovHydroIEEE2.pmin). Typical value = 1.
pminFloat1..1Minimum gate opening (Pmin) (<GovHydroIEEE2.pmax). Typical value = 0.
rpermFloat1..1Permanent droop (Rperm). Typical value = 0,05.
rtempFloat1..1Temporary droop (Rtemp). Typical value = 0,5.
tgFloat1..1Gate servo time constant (Tg) (>= 0). Typical value = 0,5.
tpFloat1..1Pilot servo valve time constant (Tp) (>= 0). Typical value = 0,03.
trFloat1..1Dashpot time constant (Tr) (>= 0). Typical value = 12.
twFloat1..1Water inertia time constant (Tw) (>= 0). Typical value = 2.
ucFloat1..1Maximum gate closing velocity (Uc) (<0). Typical value = -0,1.
uoFloat1..1Maximum gate opening velocity (Uo). Unit = PU / s. Typical value = 0,1.