GovHydro3

Modified IEEE hydro governor-turbine. This model differs from that defined in the IEEE modelling guideline paper in that the limits on gate position and velocity do not permit 'wind up' of the upstream signals.

Inheritance

Attributes

LabelTypeMultiplicityComment
atFloat1..1Turbine gain (At) (>0). Typical value = 1,2.
db1Float1..1Intentional dead-band width (db1). Unit = Hz. Typical value = 0.
db2Float1..1Unintentional dead-band (db2). Unit = MW. Typical value = 0.
dturbFloat1..1Turbine damping factor (Dturb). Typical value = 0,2.
epsFloat1..1Intentional db hysteresis (eps). Unit = Hz. Typical value = 0.
governorControlBoolean1..1Governor control flag (Cflag). true = PID control is active false = double derivative control is active. Typical value = true.
gv1Float1..1Nonlinear gain point 1, PU gv (Gv1). Typical value = 0.
gv2Float1..1Nonlinear gain point 2, PU gv (Gv2). Typical value = 0.
gv3Float1..1Nonlinear gain point 3, PU gv (Gv3). Typical value = 0.
gv4Float1..1Nonlinear gain point 4, PU gv (Gv4). Typical value = 0.
gv5Float1..1Nonlinear gain point 5, PU gv (Gv5). Typical value = 0.
gv6Float1..1Nonlinear gain point 6, PU gv (Gv6). Typical value = 0.
h0Float1..1Turbine nominal head (H0). Typical value = 1.
k1Float1..1Derivative gain (K1). Typical value = 0,01.
k2Float1..1Double derivative gain, if Cflag = -1 (K2). Typical value = 2,5.
kgFloat1..1Gate servo gain (Kg). Typical value = 2.
kiFloat1..1Integral gain (Ki). Typical value = 0,5.
mwbaseFloat1..1Base for power values (MWbase) (> 0). Unit = MW.
pgv1Float1..1Nonlinear gain point 1, PU power (Pgv1). Typical value = 0.
pgv2Float1..1Nonlinear gain point 2, PU power (Pgv2). Typical value = 0.
pgv3Float1..1Nonlinear gain point 3, PU power (Pgv3). Typical value = 0.
pgv4Float1..1Nonlinear gain point 4, PU power (Pgv4). Typical value = 0.
pgv5Float1..1Nonlinear gain point 5, PU power (Pgv5). Typical value = 0.
pgv6Float1..1Nonlinear gain point 6, PU power (Pgv6). Typical value = 0.
pmaxFloat1..1Maximum gate opening, PU of MWbase (Pmax) (> GovHydro3.pmin). Typical value = 1.
pminFloat1..1Minimum gate opening, PU of MWbase (Pmin) (< GovHydro3.pmax). Typical value = 0.
qnlFloat1..1No-load turbine flow at nominal head (Qnl). Typical value = 0,08.
relecFloat1..1Steady-state droop, PU, for electrical power feedback (Relec). Typical value = 0,05.
rgateFloat1..1Steady-state droop, PU, for governor output feedback (Rgate). Typical value = 0.
tdFloat1..1Input filter time constant (Td) (>= 0). Typical value = 0,05.
tfFloat1..1Washout time constant (Tf) (>= 0). Typical value = 0,1.
tpFloat1..1Gate servo time constant (Tp) (>= 0). Typical value = 0,05.
ttFloat1..1Power feedback time constant (Tt) (>= 0). Typical value = 0,2.
twFloat1..1Water inertia time constant (Tw) (>= 0). If = 0, block is bypassed. Typical value = 1.
velclFloat1..1Maximum gate closing velocity (Velcl). Unit = PU / s. Typical value = -0,2.
velopFloat1..1Maximum gate opening velocity (Velop). Unit = PU / s. Typical value = 0,2.