Skip to main content

GovHydro1

Basic hydro turbine governor.

Inheritance

Attributes

LabelTypeMultiplicityComment
atFloat1..1Turbine gain (At) (> 0). Typical value = 1,2.
dturbFloat1..1Turbine damping factor (Dturb) (>= 0). Typical value = 0,5.
gmaxFloat1..1Maximum gate opening (Gmax) (> 0 and > GovHydro.gmin). Typical value = 1.
gminFloat1..1Minimum gate opening (Gmin) (>= 0 and < GovHydro1.gmax). Typical value = 0.
hdamFloat1..1Turbine nominal head (hdam). Typical value = 1.
mwbaseFloat1..1Base for power values (MWbase) (> 0). Unit = MW.
qnlFloat1..1No-load flow at nominal head (qnl) (>= 0). Typical value = 0,08.
rpermFloat1..1Permanent droop (R) (> 0). Typical value = 0,04.
rtempFloat1..1Temporary droop (r) (> GovHydro1.rperm). Typical value = 0,3.
tfFloat1..1Filter time constant (Tf) (> 0). Typical value = 0,05.
tgFloat1..1Gate servo time constant (Tg) (> 0). Typical value = 0,5.
trFloat1..1Washout time constant (Tr) (> 0). Typical value = 5.
twFloat1..1Water inertia time constant (Tw) (> 0). Typical value = 1.
velmFloat1..1Maximum gate velocity (Vlem) (> 0). Typical value = 0,2.