Skip to main content

GovGASTWD

Woodward™ gas turbine governor. [Footnote: Woodward gas turbines are an example of suitable products available commercially. This information is given for the convenience of users of this document and does not constitute an endorsement by IEC of these products.]

Inheritance

Attributes

LabelTypeMultiplicityComment
aFloat1..1Valve positioner (A).
af1Float1..1Exhaust temperature parameter (Af1).
af2Float1..1Coefficient equal to 0,5(1-speed) (Af2).
bFloat1..1Valve positioner (B).
bf1Float1..1(Bf1). Bf1 = E(1-w) where E (speed sensitivity coefficient) is 0,55 to 0,65 x Tr.
bf2Float1..1Turbine torque coefficient Khhv (depends on heating value of fuel stream in combustion chamber) (Bf2).
cFloat1..1Valve positioner (C).
cf2Float1..1Coefficient defining fuel flow where power output is 0 % (Cf2). Synchronous but no output. Typically 0,23 x Khhv (23 % fuel flow).
ecrFloat1..1Combustion reaction time delay (Ecr) (>= 0).
etdFloat1..1Turbine and exhaust delay (Etd) (>= 0).
k3Float1..1Ratio of fuel adjustment (K3).
k4Float1..1Gain of radiation shield (K4).
k5Float1..1Gain of radiation shield (K5).
k6Float1..1Minimum fuel flow (K6).
kdFloat1..1Drop governor gain (Kd).
kdroopFloat1..1(Kdroop) (>= 0).
kfFloat1..1Fuel system feedback (Kf).
kiFloat1..1Isochronous Governor Gain (Ki).
kpFloat1..1PID proportional gain (Kp).
mwbaseFloat1..1Base for power values (MWbase) (> 0). Unit = MW.
tFloat1..1Fuel control time constant (T) (>= 0).
t3Float1..1Radiation shield time constant (T3) (>= 0).
t4Float1..1Thermocouple time constant (T4) (>= 0).
t5Float1..1Temperature control time constant (T5) (>= 0).
tcFloat1..1Temperature control (Tc).
tcdFloat1..1Compressor discharge time constant (Tcd) (>= 0).
tdFloat1..1Power transducer time constant (Td) (>= 0).
tfFloat1..1Fuel system time constant (Tf) (>= 0).
tmaxFloat1..1Maximum Turbine limit (Tmax) (> GovGASTWD.tmin).
tminFloat1..1Minimum turbine limit (Tmin) (< GovGASTWD.tmax).
trFloat1..1Rated temperature (Tr).
trateFloat1..1Turbine rating (Trate). Unit = MW.
ttFloat1..1Temperature controller integration rate (Tt) (>= 0).