Skip to main content

GovGAST4

Generic turbogas.

Inheritance

Attributes

LabelTypeMultiplicityComment
bpFloat1..1Droop (bp). Typical value = 0,05.
ktmFloat1..1Compressor gain (Ktm). Typical value = 0.
mnefFloat1..1Fuel flow maximum negative error value (MNef). Typical value = -0,05.
mxefFloat1..1Fuel flow maximum positive error value (MXef). Typical value = 0,05.
rymnFloat1..1Minimum valve opening (RYMN). Typical value = 0.
rymxFloat1..1Maximum valve opening (RYMX). Typical value = 1,1.
taFloat1..1Maximum gate opening velocity (TA) (>= 0). Typical value = 3.
tcFloat1..1Maximum gate closing velocity (TC) (>= 0). Typical value = 0,5.
tcmFloat1..1Fuel control time constant (Tcm) (>= 0). Typical value = 0,1.
tmFloat1..1Compressor discharge volume time constant (Tm) (>= 0). Typical value = 0,2.
tyFloat1..1Time constant of fuel valve positioner (Ty) (>= 0). Typical value = 0,1.