Generic turbogas with acceleration and temperature controller.

Inheritance

Attributes

LabelTypeMultiplicityComment
bcaFloat1..1Acceleration limit set-point (Bca). Unit = 1/s. Typical value = 0,01.
bpFloat1..1Droop (bp). Typical value = 0,05.
dtcFloat1..1Exhaust temperature variation due to fuel flow increasing from 0 to 1 PU (deltaTc). Typical value = 390.
kaFloat1..1Minimum fuel flow (Ka). Typical value = 0,23.
kacFloat1..1Fuel system feedback (KAC). Typical value = 0.
kcaFloat1..1Acceleration control integral gain (Kca). Unit = 1/s. Typical value = 100.
ksiFloat1..1Gain of radiation shield (Ksi). Typical value = 0,8.
kyFloat1..1Coefficient of transfer function of fuel valve positioner (Ky). Typical value = 1.
mnefFloat1..1Fuel flow maximum negative error value (MNef). Typical value = -0,05.
mxefFloat1..1Fuel flow maximum positive error value (MXef). Typical value = 0,05.
rcmnFloat1..1Minimum fuel flow (RCMN). Typical value = -0,1.
rcmxFloat1..1Maximum fuel flow (RCMX). Typical value = 1.
tacFloat1..1Fuel control time constant (Tac) (>= 0). Typical value = 0,1.
tcFloat1..1Compressor discharge volume time constant (Tc) (>= 0). Typical value = 0,2.
tdFloat1..1Temperature controller derivative gain (Td) (>= 0). Typical value = 3,3.
tfenFloat1..1Turbine rated exhaust temperature correspondent to Pm=1 PU (Tfen). Typical value = 540.
tgFloat1..1Time constant of speed governor (Tg) (>= 0). Typical value = 0,05.
tsiFloat1..1Time constant of radiation shield (Tsi) (>= 0). Typical value = 15.
ttFloat1..1Temperature controller integration rate (Tt). Typical value = 250.
ttcFloat1..1Time constant of thermocouple (Ttc) (>= 0). Typical value = 2,5.
tyFloat1..1Time constant of fuel valve positioner (Ty) (>= 0). Typical value = 0,2.