Modified single shaft gas turbine.

Inheritance

Attributes

LabelTypeMultiplicityComment
aFloat1..1Turbine power time constant numerator scale factor (a). Typical value = 0,8.
bFloat1..1Turbine power time constant denominator scale factor (b) (>0). Typical value = 1.
db1Float1..1Intentional dead-band width (db1). Unit = Hz. Typical value = 0.
db2Float1..1Unintentional dead-band (db2). Unit = MW. Typical value = 0.
epsFloat1..1Intentional db hysteresis (eps). Unit = Hz. Typical value = 0.
fidleFloat1..1Fuel flow at zero power output (Fidle). Typical value = 0,18.
gv1Float1..1Nonlinear gain point 1, PU gv (Gv1). Typical value = 0.
gv2Float1..1Nonlinear gain point 2,PU gv (Gv2). Typical value = 0.
gv3Float1..1Nonlinear gain point 3, PU gv (Gv3). Typical value = 0.
gv4Float1..1Nonlinear gain point 4, PU gv (Gv4). Typical value = 0.
gv5Float1..1Nonlinear gain point 5, PU gv (Gv5). Typical value = 0.
gv6Float1..1Nonlinear gain point 6, PU gv (Gv6). Typical value = 0.
kaFloat1..1Governor gain (Ka). Typical value = 0.
ktFloat1..1Temperature limiter gain (Kt). Typical value = 3.
lmaxFloat1..1Ambient temperature load limit (Lmax). Lmax is the turbine power output corresponding to the limiting exhaust gas temperature. Typical value = 1.
loadincFloat1..1Valve position change allowed at fast rate (Loadinc). Typical value = 0,05.
ltrateFloat1..1Maximum long term fuel valve opening rate (Ltrate). Typical value = 0,02.
mwbaseFloat1..1Base for power values (MWbase) (> 0). Unit = MW.
pgv1Float1..1Nonlinear gain point 1, PU power (Pgv1). Typical value = 0.
pgv2Float1..1Nonlinear gain point 2, PU power (Pgv2). Typical value = 0.
pgv3Float1..1Nonlinear gain point 3, PU power (Pgv3). Typical value = 0.
pgv4Float1..1Nonlinear gain point 4, PU power (Pgv4). Typical value = 0.
pgv5Float1..1Nonlinear gain point 5, PU power (Pgv5). Typical value = 0.
pgv6Float1..1Nonlinear gain point 6, PU power (Pgv6). Typical value = 0.
rFloat1..1Permanent droop (R) (>0). Typical value = 0,04.
rmaxFloat1..1Maximum fuel valve opening rate (Rmax). Unit = PU / s. Typical value = 1.
t1Float1..1Governor mechanism time constant (T1) (>= 0). T1 represents the natural valve positioning time constant of the governor for small disturbances, as seen when rate limiting is not in effect. Typical value = 0,5.
t2Float1..1Turbine power time constant (T2) (>= 0). T2 represents delay due to internal energy storage of the gas turbine engine. T2 can be used to give a rough approximation to the delay associated with acceleration of the compressor spool of a multi-shaft engine, or with the compressibility of gas in the plenum of the free power turbine of an aero-derivative unit, for example. Typical value = 0,5.
t3Float1..1Turbine exhaust temperature time constant (T3) (>= 0). T3 represents delay in the exhaust temperature and load limiting system. Typical value = 3.
t4Float1..1Governor lead time constant (T4) (>= 0). Typical value = 0.
t5Float1..1Governor lag time constant (T5) (>= 0). If = 0, entire gain and lead-lag block is bypassed. Typical value = 0.
tltrFloat1..1Valve position averaging time constant (Tltr) (>= 0). Typical value = 10.
vmaxFloat1..1Maximum turbine power, PU of MWbase (Vmax) (> GovGAST1.vmin). Typical value = 1.