Single shaft gas turbine.

Inheritance

Attributes

LabelTypeMultiplicityComment
atFloat1..1Ambient temperature load limit (Load Limit). Typical value = 1.
dturbFloat1..1Turbine damping factor (Dturb). Typical value = 0,18.
ktFloat1..1Temperature limiter gain (Kt). Typical value = 3.
mwbaseFloat1..1Base for power values (MWbase) (> 0). Unit = MW.
rFloat1..1Permanent droop (R) (>0). Typical value = 0,04.
t1Float1..1Governor mechanism time constant (T1) (>= 0). T1 represents the natural valve positioning time constant of the governor for small disturbances, as seen when rate limiting is not in effect. Typical value = 0,5.
t2Float1..1Turbine power time constant (T2) (>= 0). T2 represents delay due to internal energy storage of the gas turbine engine. T2 can be used to give a rough approximation to the delay associated with acceleration of the compressor spool of a multi-shaft engine, or with the compressibility of gas in the plenum of a free power turbine of an aero-derivative unit, for example. Typical value = 0,5.
t3Float1..1Turbine exhaust temperature time constant (T3) (>= 0). Typical value = 3.
vmaxFloat1..1Maximum turbine power, PU of MWbase (Vmax) (> GovGAST.vmin). Typical value = 1.
vminFloat1..1Minimum turbine power, PU of MWbase (Vmin) (< GovGAST.vmax). Typical value = 0.