ExternalNetworkInjection

This class represents the external network and it is used for IEC 60909 calculations.

Inheritance

Attributes

LabelTypeMultiplicityComment
governorSCDFloat1..1Power Frequency Bias. This is the change in power injection divided by the change in frequency and negated. A positive value of the power frequency bias provides additional power injection upon a drop in frequency.
ikSecondBoolean0..1Indicates whether initial symmetrical short-circuit current and power have been calculated according to IEC (Ik'). Used only if short circuit calculations are done according to superposition method.
maxInitialSymShCCurrentFloat1..1Maximum initial symmetrical short-circuit currents (Ik' max) in A (Ik' = Sk'/(SQRT(3) Un)). Used for short circuit data exchange according to IEC 60909.
maxPFloat1..1Maximum active power of the injection.
maxQFloat1..1Maximum reactive power limit. It is used for modelling of infeed for load flow exchange and not for short circuit modelling.
maxR0ToX0RatioFloat1..1Maximum ratio of zero sequence resistance of Network Feeder to its zero sequence reactance (R(0)/X(0) max). Used for short circuit data exchange according to IEC 60909.
maxR1ToX1RatioFloat1..1Maximum ratio of positive sequence resistance of Network Feeder to its positive sequence reactance (R(1)/X(1) max). Used for short circuit data exchange according to IEC 60909.
maxZ0ToZ1RatioFloat1..1Maximum ratio of zero sequence impedance to its positive sequence impedance (Z(0)/Z(1) max). Used for short circuit data exchange according to IEC 60909.
minInitialSymShCCurrentFloat1..1Minimum initial symmetrical short-circuit currents (Ik' min) in A (Ik' = Sk'/(SQRT(3) Un)). Used for short circuit data exchange according to IEC 60909.
minPFloat1..1Minimum active power of the injection.
minQFloat1..1Minimum reactive power limit. It is used for modelling of infeed for load flow exchange and not for short circuit modelling.
minR0ToX0RatioFloat1..1Indicates whether initial symmetrical short-circuit current and power have been calculated according to IEC (Ik'). Used for short circuit data exchange according to IEC 6090.
minR1ToX1RatioFloat1..1Minimum ratio of positive sequence resistance of Network Feeder to its positive sequence reactance (R(1)/X(1) min). Used for short circuit data exchange according to IEC 60909.
minZ0ToZ1RatioFloat1..1Minimum ratio of zero sequence impedance to its positive sequence impedance (Z(0)/Z(1) min). Used for short circuit data exchange according to IEC 60909.
pFloat1..1Active power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for steady state solutions.
qFloat1..1Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for steady state solutions.
referencePriorityInteger1..1Priority of unit for use as powerflow voltage phase angle reference bus selection. 0 = don t care (default) 1 = highest priority. 2 is less than 1 and so on.
voltageFactorFloat0..1Voltage factor in pu, which was used to calculate short-circuit current Ik' and power Sk'. Used only if short circuit calculations are done according to superposition method.