Skip to main content

ExcST7BUELselectorKind (Enumeration)

Types of connections for the UEL input used for static excitation systems type 7B.

Values​

LabelComment
noUELinputNo UEL input is used. Corresponds to UELin not = 1 and not = 2 and not = 3 on the ExcST7B diagram. Original ExcST7B model would have called this UELin = 0.
addVrefThe signal is added to Vref. Corresponds to UELin = 1 on the ExcST7B diagram.
inputHVgateThe signal is connected into the input HVGate. Corresponds to UELin = 2 on the ExcST7B diagram.