Skip to main content

ExcIEEEAC1A

IEEE 421.5-2005 type AC1A model. The model represents the field-controlled alternator-rectifier excitation systems designated type AC1A. These excitation systems consist of an alternator main exciter with non-controlled rectifiers. Reference: IEEE 421.5-2005, 6.1.

Inheritance

Attributes

LabelTypeMultiplicityComment
kaFloat1..1Voltage regulator gain (KA) (> 0). Typical value = 400.
kcFloat1..1Rectifier loading factor proportional to commutating reactance (KC) (>= 0). Typical value = 0,2.
kdFloat1..1Demagnetizing factor, a function of exciter alternator reactances (KD) (>= 0). Typical value = 0,38.
keFloat1..1Exciter constant related to self-excited field (KE). Typical value = 1.
kfFloat1..1Excitation control system stabilizer gains (KF) (>= 0). Typical value = 0,03.
seve1Float1..1Exciter saturation function value at the corresponding exciter voltage, VE1, back of commutating reactance (SE[VE1]) (>= 0). Typical value = 0,1.
seve2Float1..1Exciter saturation function value at the corresponding exciter voltage, VE2, back of commutating reactance (SE[VE2]) (>= 0). Typical value = 0,03.
taFloat1..1Voltage regulator time constant (TA) (> 0). Typical value = 0,02.
tbFloat1..1Voltage regulator time constant (TB) (>= 0). Typical value = 0.
tcFloat1..1Voltage regulator time constant (TC) (>= 0). Typical value = 0.
teFloat1..1Exciter time constant, integration rate associated with exciter control (TE) (> 0). Typical value = 0,8.
tfFloat1..1Excitation control system stabilizer time constant (TF) (> 0). Typical value = 1.
vamaxFloat1..1Maximum voltage regulator output (VAMAX) (> 0). Typical value = 14,5.
vaminFloat1..1Minimum voltage regulator output (VAMIN) (< 0). Typical value = -14,5.
ve1Float1..1Exciter alternator output voltages back of commutating reactance at which saturation is defined (VE1) (> 0). Typical value = 4,18.
ve2Float1..1Exciter alternator output voltages back of commutating reactance at which saturation is defined (VE2) (> 0). Typical value = 3,14.
vrmaxFloat1..1Maximum voltage regulator outputs (VRMAX) (> 0). Typical value = 6,03.
vrminFloat1..1Minimum voltage regulator outputs (VRMIN) (< 0). Typical value = -5,43.