Skip to main content

ExcELIN2

Detailed excitation system ELIN (VATECH). This model represents an all-static excitation system. A PI voltage controller establishes a desired field current set point for a proportional current controller. The integrator of the PI controller has a follow-up input to match its signal to the present field current. Power system stabilizer models used in conjunction with this excitation system model: PssELIN2, PssIEEE2B, Pss2B.

Inheritance

Attributes

LabelTypeMultiplicityComment
efdbasFloat1..1Gain (Efdbas). Typical value = 0,1.
iefmaxFloat1..1Limiter (Iefmax) (> ExcELIN2.iefmin). Typical value = 1.
iefmax2Float1..1Minimum open circuit excitation voltage (Iefmax2). Typical value = -5.
iefminFloat1..1Limiter (Iefmin) (< ExcELIN2.iefmax). Typical value = 1.
k1Float1..1Voltage regulator input gain (K1). Typical value = 0.
k1ecFloat1..1Voltage regulator input limit (K1ec). Typical value = 2.
k2Float1..1Gain (K2). Typical value = 5.
k3Float1..1Gain (K3). Typical value = 0,1.
k4Float1..1Gain (K4). Typical value = 0.
kd1Float1..1Voltage controller derivative gain (Kd1). Typical value = 34,5.
ke2Float1..1Gain (Ke2). Typical value = 0,1.
ketbFloat1..1Gain (Ketb). Typical value = 0,06.
pid1maxFloat1..1Controller follow up gain (PID1max). Typical value = 2.
seve1Float1..1Exciter saturation function value at the corresponding exciter voltage, Ve1, back of commutating reactance (Se[Ve1]) (>= 0). Typical value = 0.
seve2Float1..1Exciter saturation function value at the corresponding exciter voltage, Ve2, back of commutating reactance (Se[Ve2]) (>= 0). Typical value = 1.
tb1Float1..1Voltage controller derivative washout time constant (Tb1) (>= 0). Typical value = 12,45.
teFloat1..1Time constant (Te) (>= 0). Typical value = 0.
te2Float1..1Time Constant (Te2) (>= 0). Typical value = 1.
ti1Float1..1Controller follow up deadband (Ti1). Typical value = 0.
ti3Float1..1Time constant (Ti3) (>= 0). Typical value = 3.
ti4Float1..1Time constant (Ti4) (>= 0). Typical value = 0.
tr4Float1..1Time constant (Tr4) (>= 0). Typical value = 1.
upmaxFloat1..1Limiter (Upmax) (> ExcELIN2.upmin). Typical value = 3.
upminFloat1..1Limiter (Upmin) (< ExcELIN2.upmax). Typical value = 0.
ve1Float1..1Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve1) (> 0). Typical value = 3.
ve2Float1..1Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve2) (> 0). Typical value = 0.
xpFloat1..1Excitation transformer effective reactance (Xp). Typical value = 1.