Skip to main content

ExcELIN1

Static PI transformer fed excitation system ELIN (VATECH) - simplified model. This model represents an all-static excitation system. A PI voltage controller establishes a desired field current set point for a proportional current controller. The integrator of the PI controller has a follow-up input to match its signal to the present field current. A power system stabilizer with power input is included in the model.

Inheritance

Attributes

LabelTypeMultiplicityComment
dpnfFloat1..1Controller follow up deadband (Dpnf). Typical value = 0.
efmaxFloat1..1Maximum open circuit excitation voltage (Efmax) (> ExcELIN1.efmin). Typical value = 5.
efminFloat1..1Minimum open circuit excitation voltage (Efmin) (< ExcELIN1.efmax). Typical value = -5.
ks1Float1..1Stabilizer gain 1 (Ks1). Typical value = 0.
ks2Float1..1Stabilizer gain 2 (Ks2). Typical value = 0.
smaxFloat1..1Stabilizer limit output (smax). Typical value = 0,1.
tfiFloat1..1Current transducer time constant (Tfi) (>= 0). Typical value = 0.
tnuFloat1..1Controller reset time constant (Tnu) (>= 0). Typical value = 2.
ts1Float1..1Stabilizer phase lag time constant (Ts1) (>= 0). Typical value = 1.
ts2Float1..1Stabilizer filter time constant (Ts2) (>= 0). Typical value = 1.
tswFloat1..1Stabilizer parameters (Tsw) (>= 0). Typical value = 3.
vpiFloat1..1Current controller gain (Vpi). Typical value = 12,45.
vpnfFloat1..1Controller follow up gain (Vpnf). Typical value = 2.
vpuFloat1..1Voltage controller proportional gain (Vpu). Typical value = 34,5.
xeFloat1..1Excitation transformer effective reactance (Xe) (>= 0). Xe represents the regulation of the transformer/rectifier unit. Typical value = 0,06.