Skip to main content

ExcAC3A

Modified IEEE AC3A alternator-supplied rectifier excitation system with different field current limit.

Inheritance

Attributes

LabelTypeMultiplicityComment
efdnFloat1..1Value of Efd at which feedback gain changes (Efdn) (> 0). Typical value = 2,36.
kaFloat1..1Voltage regulator gain (Ka) (> 0). Typical value = 45,62.
kcFloat1..1Rectifier loading factor proportional to commutating reactance (Kc) (>= 0). Typical value = 0,104.
kdFloat1..1Demagnetizing factor, a function of exciter alternator reactances (Kd) (>= 0). Typical value = 0,499.
keFloat1..1Exciter constant related to self-excited field (Ke). Typical value = 1.
kfFloat1..1Excitation control system stabilizer gains (Kf) (>= 0). Typical value = 0,143.
kf1Float1..1Coefficient to allow different usage of the model (Kf1). Typical value = 1.
kf2Float1..1Coefficient to allow different usage of the model (Kf2). Typical value = 0.
klvFloat1..1Gain used in the minimum field voltage limiter loop (Klv). Typical value = 0,194.
knFloat1..1Excitation control system stabilizer gain (Kn) (>= 0). Typical value =0,05.
krFloat1..1Constant associated with regulator and alternator field power supply (Kr) (> 0). Typical value =3,77.
ksFloat1..1Coefficient to allow different usage of the model-speed coefficient (Ks). Typical value = 0.
seve1Float1..1Exciter saturation function value at the corresponding exciter voltage, Ve1, back of commutating reactance (Se[Ve1]) (>= 0). Typical value = 1,143.
seve2Float1..1Exciter saturation function value at the corresponding exciter voltage, Ve2, back of commutating reactance (Se[Ve2]) (>= 0). Typical value = 0,1.
taFloat1..1Voltage regulator time constant (Ta) (> 0). Typical value = 0,013.
tbFloat1..1Voltage regulator time constant (Tb) (>= 0). Typical value = 0.
tcFloat1..1Voltage regulator time constant (Tc) (>= 0). Typical value = 0.
teFloat1..1Exciter time constant, integration rate associated with exciter control (Te) (> 0). Typical value = 1,17.
tfFloat1..1Excitation control system stabilizer time constant (Tf) (> 0). Typical value = 1.
vamaxFloat1..1Maximum voltage regulator output (Vamax) (> 0). Typical value = 1.
vaminFloat1..1Minimum voltage regulator output (Vamin) (< 0). Typical value = -0,95.
ve1Float1..1Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve1) (> 0). Typical value = 6.24.
ve2Float1..1Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve2) (> 0). Typical value = 4,68.
veminFloat1..1Minimum exciter voltage output (Vemin) (<= 0). Typical value = 0.
vfemaxFloat1..1Exciter field current limit reference (Vfemax) (>= 0). Typical value = 16.
vlvFloat1..1Field voltage used in the minimum field voltage limiter loop (Vlv). Typical value = 0,79.