Skip to main content

ExcAC2A

Modified IEEE AC2A alternator-supplied rectifier excitation system with different field current limit.

Inheritance

Attributes

LabelTypeMultiplicityComment
hvgateBoolean1..1Indicates if HV gate is active (HVgate). true = gate is used false = gate is not used. Typical value = true.
kaFloat1..1Voltage regulator gain (Ka) (> 0). Typical value = 400.
kbFloat1..1Second stage regulator gain (Kb) (> 0). Exciter field current controller gain. Typical value = 25.
kb1Float1..1Second stage regulator gain (Kb1). It is exciter field current controller gain used as alternative to Kb to represent a variant of the ExcAC2A model. Typical value = 25.
kcFloat1..1Rectifier loading factor proportional to commutating reactance (Kc) (>= 0). Typical value = 0,28.
kdFloat1..1Demagnetizing factor, a function of exciter alternator reactances (Kd) (>= 0). Typical value = 0,35.
keFloat1..1Exciter constant related to self-excited field (Ke). Typical value = 1.
kfFloat1..1Excitation control system stabilizer gains (Kf) (>= 0). Typical value = 0,03.
khFloat1..1Exciter field current feedback gain (Kh) (>= 0). Typical value = 1.
klFloat1..1Exciter field current limiter gain (Kl). Typical value = 10.
kl1Float1..1Coefficient to allow different usage of the model (Kl1). Typical value = 1.
ksFloat1..1Coefficient to allow different usage of the model-speed coefficient (Ks) (>= 0). Typical value = 0.
lvgateBoolean1..1Indicates if LV gate is active (LVgate). true = gate is used false = gate is not used. Typical value = true.
seve1Float1..1Exciter saturation function value at the corresponding exciter voltage, Ve1, back of commutating reactance (Se[Ve1]) (>= 0). Typical value = 0,037.
seve2Float1..1Exciter saturation function value at the corresponding exciter voltage, Ve2, back of commutating reactance (Se[Ve2]) (>= 0). Typical value = 0,012.
taFloat1..1Voltage regulator time constant (Ta) (> 0). Typical value = 0,02.
tbFloat1..1Voltage regulator time constant (Tb) (>= 0). Typical value = 0.
tcFloat1..1Voltage regulator time constant (Tc) (>= 0). Typical value = 0.
teFloat1..1Exciter time constant, integration rate associated with exciter control (Te) (> 0). Typical value = 0,6.
tfFloat1..1Excitation control system stabilizer time constant (Tf) (> 0). Typical value = 1.
vamaxFloat1..1Maximum voltage regulator output (Vamax) (> 0). Typical value = 8.
vaminFloat1..1Minimum voltage regulator output (Vamin) (< 0). Typical value = -8.
ve1Float1..1Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve1) (> 0). Typical value = 4,4.
ve2Float1..1Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve2) (> 0). Typical value = 3,3.
vfemaxFloat1..1Exciter field current limit reference (Vfemax) (>= 0). Typical value = 4,4.
vlrFloat1..1Maximum exciter field current (Vlr) (> 0). Typical value = 4,4.
vrmaxFloat1..1Maximum voltage regulator outputs (Vrmax) (> 0). Typical value = 105.
vrminFloat1..1Minimum voltage regulator outputs (Vrmin) (< 0). Typical value = -95.